
Table 7 — Potentiometer Adjustment
DIAL
ADJUSTMENT RANGE
FUNCTION
FACTORY
SETTING
Minimum
(CCW)
Maximum
(CW)
Starting Current 100% 400% Sets initial starting
current level.
100%
Ramp Time
(Adjustable
Current Ramp)
2
seconds
30
seconds
Sets time during which
current ramps from the
initial starting level to the
maximum possible
current limit setting.
10 seconds
Current Limit 100% 400% Sets maximum
starting current.
250%
Pulse Start 0 (Off) 2 seconds Sets duration of 400%
current pulse. Pulse
is used to break
load free.
OFF
Current Trip 50% 400% Sets running current trip. 175%
Power Saver — — — OFF
CCW — Counterclockwise
CW — Clockwise
Starting Current — The torque required to start a machine
(initial torque) varies from one application to another. Start-
ing current may be adjusted to match the initial motor torque
of the application. The starting current value is adjustable
from 100% to 400% FLA and is factory set at 100%. If quick
acceleration is desired, set the starting current at a higher
level.
Ramp Time (Adjustable Current Ramp) — The motor cur-
rent is ramped up from the starting current value over a timed
period set by the ramp time potentiometer (adjustable from
2 to 30 seconds at 400% current limit setting). The 23XL is
factory set at 10 seconds. However, based on jobsite con-
ditions, a range of ±5 seconds is acceptable.
Current Limit — This protection limits motor current to a
set value and holds motor torque at a reduced level during
motor start. The current limit is adjustable from 100% to 400%
of the motor full load current value. The current limit is fac-
tory set at 250%.
Pulse Start — A pulse start is not used on this machine. It is
set to the OFF position.
Current Trip —Acontrol contact closes when the motor reaches
a factory set value of 175% of full load amps. This signal is
used as an interlock to shut down the machine if the motor
stalls (increasing load).
Changing Adjustments — The settings are interdependent.
If any setting is changed, the other settings should be checked.
Check the settings in the sequence shown above.
Voltage Measurements — Consider the following when check-
ing voltage measurements:
• Before energizing the starter, check the incoming lines for
properly balanced voltages.
• Close the circuit breaker to apply power to the starter. Verify
the 120 vac control voltage.
• Visually check to ensure that all fans are running (if
applicable).
• Verify phase sequence at line terminals. Incorrect phase
sequence will result in a shunt trip of the circuit breaker.
• Verify that the phase rotation of the lines to the motor is
correct.
• If the motor is found to be rotating in the wrong direction,
interchange any two phases to the motor.
• Start the unit.
• When unit reaches full speed, monitor the running current
to ensure that the motor is not overloaded.
High Altitude Locations — Recalibration of the pres-
sure transducers will be necessary since the machine was
initially calibrated at sea level. Please see the calibration pro-
cedure in the Troubleshooting Guide section on page 68.
Input the Design Set Points — Access the LID Set
Point menu and view/modify the Base Demand Limit set point
and either the LCW set point, the ECW set point, or Ice Build
set point. The PIC can control a set point to either the leav-
ing or entering chilled water. This control method is set in
the Equipment Configuration menu Config table. See
Fig. 21.
Input the Local Occupied Schedule (OCCPC01S)
—
Access the schedule OCCPC01S screen on the LID and
set up the occupied time schedule per the customer’s re-
quirements. If no schedule is available, set it for 24 hours
occupied days per week including holidays. This is also the
default setting of the schedule. For this schedule, modify Pe-
riod 1 for ON at 0000 and OFF at 2400 and enable the pe-
riod to be in effect for all days and holidays. For more in-
formation about how to set up a time schedule, read the Controls
section, page 13.
The CCN Occupied Schedule (OCCPC03S) should be con-
figured if a CCN system is being installed or if a secondary
time schedule is required. It normally is input through the
CCN Building Supervisor, but it can also be modified at the
LID.
Fig. 39 — Typical Potentiometer Adjustment
52
Komentarze do niniejszej Instrukcji