Copyright 2010 Carrier Corporation Form 23XRV-3PD
Carrier’s Evergreen
®
23XRV chiller is
the world’s first integrated variable
speed, water-cooled, screw chiller.
It incorporates significant break-
throughs in water-cooled chiller tech-
nology to provide excellent reliability
and achieve superior efficiencies at
true operating conditions without com-
promising the environment.
The 23XRV chiller provides:
Variable speed, positive
displacement screw compressor.
Air Conditioning, Heating, and
Refrigerant Institute (AHRI) certified
efficiencies to 0.33 kW/ton (AHRI
IPLV).
Chlorine-free HFC-134a refrigerant.
IEEE-519 compliance for harmonic
distortion.
An ideal solution for constant and
variable flow pumping systems.
Features/Benefits
Quality design and con-
struction make the Evergreen
23XRV chillers the best
choice for modern, efficient
chilled water plants.
Product reliability
The 23XRV chiller uses proven tech-
nology from Carrier’s existing line of
Evergreen chillers along with innova-
tions that increase reliability. The
23XRV compressors are designed for
extremely high reliability. The ad-
vanced tri-rotor compressor features a
balanced rotor geometry and shorter
screw lengths, resulting in vastly re-
duced compressor bearing loads and a
minimum L10 compressor bearing life
in excess of 500,000 hours when op-
erated at AHRI conditions.
EVERGREEN
®
23XRV
High-Efficiency Variable Speed Screw Chiller
with FOXFIRE™ Compression Technology
50/60 Hz
HFC-134a
300 to 550 Nominal Tons (1055 to 1934 Nominal kW)
Product
Data
23XRV
®
Przeglądanie stron 0
1 2 3 4 5 6 ... 31 32

Podsumowanie treści

Strona 1 - Features/Benefits

Copyright 2010 Carrier Corporation Form 23XRV-3PDCarrier’s Evergreen® 23XRV chiller is the world’s first integrated variable speed, water-cooled, scre

Strona 2 - Table of contents

10VFD FRAME SIZES*Maximum limits only. Additional application limits apply that will reduce these ampacities.AUXILIARY RATINGS**Factory wired to VFD.†

Strona 3 - Microprocessor controls

11Microprocessor controlsMicroprocessor controls provide the safety, interlock, ca-pacity control, indications and accessibility necessary toopera

Strona 4 - Model number nomenclature

12Controls (cont)CONTROL PANEL DISPLAY (Front View)ICVC ENGLISH DISPLAY IN SI UNITSCONTROL PANEL DISPLAY (Front View)ICVC CHINESE DISPLAY IN METRIC UN

Strona 5 - Physical data

13BLACKWHITEREDBLACKWHITEREDDRAIN WIREDRAIN WIREBLACKWHITEREDBLACKWHITEREDDRAIN WIREGROUNDDRAIN WIRENOTE: Field-supplied terminal strip must be lo

Strona 6 - Physical data (cont)

14Control sequenceTo start — Local start-up (manual start-up) is initiated bypressing the LOCAL or CCN menu softkey, which is indi-cated on the defaul

Strona 7 - Options and accessories

15Typical piping and wiring111678TO CHILLED LIQUID PUMPTO CONDENSER LIQUID PUMPTO COOLING TOWER FAN21MAIN COMPRESSORMOTOR POWERFROMCOOLINGTOWERFRO

Strona 8 - Dimensions

16Control wiring schematic23XRV COMPONENT ARRANGEMENTLEGENDCCM — Chiller Control ModuleCCN — Carrier Comfort Network®ICVC — International Chiller Visu

Strona 9 - Performance data

17Application dataFEYY*BGAVESSELSTYP.0’-3”[76.2mm]ACCESSORYSOLEPLATE0’-01/2”[13mm]TYP.XX*VESSELSCOND.COOLERCLCLCLCD23XRV MACHINE FOOTPRINT*See det

Strona 10 - Electrical data

18Application data (cont)ELASTOMERIC PAD23XRV ISOLATION WITH ACCESSORY SOLEPLATE PACKAGETYPICAL ISOLATIONSTANDARD ISOLATIONACCESSORY SOLEPLATE DETAILV

Strona 11 - Controls

1912111098765432123XRV NOZZLE ARRANGEMENTSNOZZLE-IN-HEAD WATERBOXESFRAME 3FRAMES 4 AND 5NOZZLE ARRANGEMENT CODES FOR ALL 23XRV NOZZLE-IN-HEAD WATE

Strona 12 - Controls (cont)

2 Variable speed capacity control elimi-nates slide valves, their associated loss-es, and their potential failure modes. Component count (both rotati

Strona 13 - Field Wiring

20Application data (cont)23XRV NOZZLE ARRANGEMENTS (cont)MARINE WATERBOXESFRAME 3NOZZLE ARRANGEMENT CODESPASSCOOLER WATERBOXESPASSCONDENSER WATERBOXES

Strona 14

2123XRV WATERBOX NOZZLE SIZES (Nozzle-In-Head and Marine WaterboxesRELIEF VALVE LOCATIONS* Coolers without optional isolation require 2 relief val

Strona 15 - Typical piping and wiring

22Vent and drain connectionsNozzle-in-head waterboxes have vent and drain connec-tions on covers. Marine waterboxes have vent and drainconnections on

Strona 16 - Control wiring schematic

23Insulation23XRV MINIMUM FIELD-INSTALLED INSULATIONREQUIREMENTSFactory insulation — Thermal insulation is factory-provided to the following areas

Strona 17 - Application data

24Variable Speed Screw Chiller HVAC Guide SpecificationsSize Range: 300 to 550 Tons (1055 to 1934 kW) NominalCarrier Model Number: 23XRVPart 1 — Gener

Strona 18 - Application data (cont)

25D. Unit shall be shipped with firmly attached labels thatindicate name of manufacturer, chiller model num-ber, chiller serial number, and refrig

Strona 19 - DISCHARGE END SUCTION END

26equipment to dissipate the motor heat as perthe following formula:Btuh = (FLkW motor) (0.05) (3413)Btuh = (FLkW motor) (171)and, alternatelyTons = B

Strona 20

27input terminals as the point of common cou-pling (PCC).b. The VFD full load efficiency shall meet orexceed 97% at 100% VFD rated ampacity.c. Act

Strona 21 - RELIEF VALVE ARRANGEMENTS

28liquid refrigerant to a reduced temperature,thereby increasing the refrigeration cycleefficiency.F. Refrigerant Flow Control:To improve part load ef

Strona 22

29displayed informing the operator that thechiller is operating in ramp loading mode.l. Chilled Water Reset:The control center shall allow reset o

Strona 23 - Insulation

3• Machine room cooling requirementsassociated with air-cooled motors,which dissipate heat to the mechan-ical room.• High noise levels common wit

Strona 24 - Guide specifications

30manual rotation of the lead chiller and a stag-gered restart of the chillers after a power fail-ure. The lead/lag system shall include loadbalancing

Strona 25

3111. Cooler and Condenser Tubes:Contact a local Carrier Representative for othertube offerings.12. Cooler and Condenser Passes:Unit manufacturer

Strona 26 - Guide specifications (cont)

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Pg 3

Strona 27

4feature also allows the machine to operate at reduced capacity, rather than shut down, when key safety limits are approached.Chilled liquid reset — R

Strona 28

523XRV COMPRESSOR AND MOTOR WEIGHTSCOMPONENT WEIGHTS LEGEND23XRV HEAT EXCHANGER WEIGHTSCOND — Condenser*Rigging weights are for

Strona 29

6ADDITIONAL WEIGHTS FOR 23XRV MARINE WATERBOXES*150 psig (1034 kPa) MARINE WATERBOXES300 psig (2068 kPa) MARINE WATERBOXES*Add to cooler and condenser

Strona 30

7*Factory-installed.†Field-installed.**Standard waterbox nozzles are victaulic type. Flanged nozzles areavailable as an option with either nozzle-

Strona 31

823XRV DIMENSIONS (NOZZLE-IN-HEAD WATERBOX)23XRV DIMENSIONS (MARINE WATERBOX)*Assumes both cooler and condenser nozzles on same end of chiller. †1 or

Strona 32 - Section 9

9NOZZLE SIZE23XRV HEAT EXCHANGER MIN/MAX FLOW RATES*ENGLISH (GPM)*Flow rates based on standard tubes in the cooler and condenser. Minimum flow bas