Table 10 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
L. MACHINE ALERTS
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/
PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
RECYCLE ALERT HIGH AMPS AT SHUTDOWN* HighAmps at Recycle: Check slide
valve.
Check that slide valve is opening. Check
motor amps correction calibration is
correct.
SENSOR FAULT ALERT LEAVING COND WATER TEMP Sensor Fault: Check leaving con-
denser water sensor.
Check sensor: See sensor test
procedure.
SENSOR FAULT ALERT ENTERING COND WATER TEMP Sensor Fault: Check entering con-
denser water sensor.
DIRTY OIL FILTER
ALERT
HIGH OIL PRESSURE DROP Replace oil filter. Condenser pressure minus oil filter pres-
sure alert greater than oil pressure trans-
ducer. Reconfigure oil filter pressure alert
on Service1 or change oil filter.
AUTORESTART PENDING POWER LOSS V P Power Loss: Check voltage
supply.
Check power supply if there are exces-
sive compressor starts occuring.
AUTORESTART PENDING LOW LINE VOLTAGE V P VALUE exceeded limit of
[LIMIT]†. Check voltage supply.
AUTORESTART PENDING HIGH LINE VOLTAGE V P VALUE exceeded limit of
[LIMIT]†. Check voltage supply.
SENSOR ALERT HIGH DISCHARGE TEMP CMPD VALUE exceeded limit of
[LIMIT]†. Check oil temperature.
Discharge temperature exceeded the alert
threshold. Check entering condenser wa-
ter temperature.
SENSOR ALERT LOW OIL PRESSURE OILPD VALUE exceeded limit of
[LIMIT]†. Low oil pressure alert.
Check that oil pressure transducer and/or
evaporator pressure transducer are not out
of range. Check entering condenser wa-
ter temperature.
CONDENSER PRESSURE
ALERT
PUMP RELAY ENERGIZED CRP High Condenser Pressure,
[VALUE] Pump energized to re-
duce pressure.
Check ambient conditions. Check con-
denser pressure for accuracy.
RECYCLE ALERT EXCESSIVE RECYCLE STARTS EXCESSIVE RECYCLE STARTS The machine load is too small to keep the
machine on line. More than 5 restarts have
occurred in 4 hours. Increase machine load,
adjust hot gas bypass, increase RECYCLE
RESTART DELTA T temperature. Do not
start chiller until minimum load is avail-
able.
POTENTIAL FREEZE-UP COND PRESS/TEMP TOO LOW CONDENSER freeze-up
protection.
Check condenser water pump operation.
Refer to Condenser Freeze Protection sec-
tion on page 31.
*Only applicable PSIO Software Version 13 and lower.
†[LIMIT] is shown on the LID as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert.
M. SPARE SENSOR ALERT MESSAGES
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/
PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
SPARE SENSOR ALERT COMMON CHWS SENSOR Sensor Fault: Check common
CHWS sensor.
Check alert temperature set points on Equip-
ment Service Service2 LID screen.
Check sensor for accuracy if reading is not
accurate.
SPARE SENSOR ALERT COMMON CHWR SENSOR Sensor Fault: Check common
CHWR sensor.
SPARE SENSOR ALERT REMOTE RESET SENSOR Sensor Fault: Check remote reset
temperature sensor.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 1 Sensor Fault: Check temperature
sensor — Spare 1.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 2 Sensor Fault: Check temperature
sensor — Spare 2.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 3 Sensor Fault: Check temperature
sensor — Spare 3.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 4 Sensor Fault: Check temperature
sensor — Spare 4.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 5 Sensor Fault: Check temperature
sensor — Spare 5.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 6 Sensor Fault: Check temperature
sensor — Spare 6.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 7 Sensor Fault: Check temperature
sensor — Spare 7.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 8 Sensor Fault: Check temperature
sensor — Spare 8.
SPARE SENSOR ALERT TEMP SENSOR — SPARE 9 Sensor Fault: Check temperature
sensor — Spare 9.