Table 4 Protective Limits and Control Settings
MONITORED PARAMETER LIMIT APPLICABLE COMMENTS
TEMPERATURE SENSORS
OUT OF RANGE
−40 to 245 F (−40 to 118.3 C) Must be outside range for 3 seconds
PRESSURE TRANSDUCERS
OUT OF RANGE
0.06 to 0.98 Voltage Ratio
Must be outside range for 3 seconds.
Ratio = Input Voltage ÷ Voltage Reference
COMPRESSOR DISCHARGE
TEMPERATURE
.200 F (93 C) Preset; alert setting configurable
LOW DISCHARGE SUPERHEAT
Oil sump temp −condenser refrigerant temp is less
than 20 F (11.1 C). Only applicable to Frame 1 and 2 machines.
Preset monitored 30 minutes after start-up
completion must be outside range for
10 consecutive minutes.
CONDENSER FREEZE PROTECTION
Energizes condenser pump relay if condenser refrigerant
temperature or condenser entering water temperature is below
the configured condenser freeze point temperature. Deenergizes
when the temperature is5F(3C)above condenser freeze point
temperature
CONDENSER FREEZE POINT configured in
Service01 table with a default setting of 34 F (1 C).
MOTOR WINDING TEMPERATURE .220 F (104.4 C) Preset; alert setting configurable
PHASE REVERSAL
(MOTOR ROTATION)
,Start-up condenser pressure - 5 psi (34.5 kPa)
Preset; must be outside range for 3 seconds
monitored after compressor motor current . 10%
EVAPORATOR REFRIGERANT
TEMPERATURE
,33 F (0.6 C) for water chilling
Preset; configure chilled medium for water
(Service1 table)
, F below Design Refrigerant Temperature
(set point adjustable from 8 to 40 F [−13 to 4 C]
for brine chilling)
Configure chilled medium for brine (Service1
screen). Adjust brine refrigerant trippoint for
proper cutout
TRANSDUCER VOLTAGE ,4.5 vdc, . 5.5 vdc Preset
CONDENSER PRESSURE .260 psig (1793 kPa) Preset; alert setting configurable
OIL PRESSURE:
Dirty Oil Filter
Oil pressure transducer less than condenser pressure oil filer
pressure alert starting 40 seconds after motor current
. 10% and oil pressure verified
Must be outside range for 3 seconds; oil pressure
alert setting configurable from 15 - 30 psi
(103.4 - 206.8 kPa) on Service1 table
Oil pressure transducer less than condenser pressure
110 psi (758 kPa) starting 40 seconds after motor current . 10%
and oil pressure verified
Must be outside range for 3 seconds
Low Oil Pressure
,Required oil pressure + 5 psi (34.5 kPa) starting
60 seconds after motor current . 10%
Ramp-up rate. See Table 1.
,Required oil pressure starting 120 seconds
after motor current . 10%
Minimum required oil pressure based on system
pressure ratio is between 20 psi (137.9 kPa)
[7 psi (48 kPa)] and 40 psi (275.8 kPa)
OIL LEVEL Discrete Preset; must be outside range for 15 seconds
LINE VOLTAGE HIGH .110% for one minute
Preset LOW ,90% and .85% for one minute or <85% for 3 seconds
SINGLE-CYCLE ,50% for one cycle
COMPRESSOR MOTOR LOAD
.110% for 10-30 seconds
Preset,10% with compressor running
.10% with compressor off
STARTER ACCELERATION TIME
(Determined by inrush current
going below 100% compressor
motor load)
.15 seconds
For machines with reduced voltage mechanical
and solid state starters
.5 seconds
For machines with full voltage starters
(Configured on Service1 table)
STARTER TRANSITION .30 seconds
For machines with reduced voltage
starters and solid-state starters
Flow Switch (Field Supplied)
Operate water pumps with machine off. Manually reduce water flow
and observe switch for proper cutout. Safety shutdown occurs when
cutout time exceeds 3 seconds. Switches are required to be rated
electronically at 24 vdc.
CUT-OUT
SETTING
ADJUSTMENT
SCREW
30