AQUASNAP ®
30RB060-390
Air-Cooled Chillers
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1
INTRODUCTION .................................. 2
INSTALLATION ................................ 2-69
Storage .......................................... 2
Step 1 -- Place, Rig and Mount Unit ............. 2
PLACING UNIT
MOUNTING UNIT
RIGGING UNIT
Step 2 -- Remove Compressor Rack
Holddown Bolts ............................... 36
Step 3 -- Remove Compressor Shipping
Braces ..................................... 36
FOR UNITS WITH COMPRESSOR SOUND BLAN-
KETS
Step 4 -- Make Cooler Fluid, Heat Reclaim and
Drain Piping Connections ..................... 36
FREEZE PROTECTION
UNITS WITH HYDRONIC PUMP PACKAGE
UNITS WITHOUT HYDRONIC PUMP PACKAGE
UNITS WITH OPTIONAL HEAT RECLAIM
HEAD PRESSURE CONTROL
FOR ALL UNITS
Step 5 -- Fill the Chilled Water and Heat Reclaim
Loop ......................................... 42
WATER SYSTEM CLEANING
WATER TREATMENT
SYSTEM PRESSURIZATION
FILLINGTHE SYSTEM(S)
SET WATER FLOW RATE
PUMP MODIFICATION/TRIMMING
PUMP VFD
SENSORLESS CONTROL (CLOSED LOOP)
REMOTE SENSOR (CLOSED LOOP)
REMOTE CONTROLLER (OPEN LOOP)
PREPARATION FOR YEAR-ROUND
OPERATION
FREEZE PROTECTION
PREPARATION FOR WINTER SHUTDOWN
CHILLED WATER SYSTEM
HEAT RECLAIM SYSTEM
Step 6 -- Make Electrical Connections .......... 53
POWER SUPPLY
POWER WIRING
CONTROL POWER
FIELD CONTROL OPTION WIRING
DUAL CHILLER CONTROL OPTION
CARRIER COMFORT NETWORK -R:
COMMUNICATION BUS WIRING
NON-CCN COMMUNICATION WIRING
Step 7 -- Install Accessories .................... 66
NAVIGATOR TM DISPLAY
REMOTE ENHANCED DISPLAY
LOW AMBIENT TEMPERATURE OPERATION
MINIMUM LOAD ACCESSORY
UNIT SECURITY/PROTECTION ACCESSORIES
COMMUNICATION ACCESSORIES
SERVICE OPTIONS
Page
Refrigerant Circuit .............................. 67
LEAK TESTING
DEHYDRATION
REFRIGERANT CHARGE
Optional BACnet Communication Wiring ........ 67
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning
equipment can be hazardous due to system pressures, electrical
components, and equipment location.
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment.
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils. All other operations should be
performed by trained service personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes.
Keep quenching cloth and fire extinguisher nearby when
brazing.
Wear safety glasses and work gloves.
Use care in handling, rigging, and setting bulky
equipment.
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
IMPORTANT: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with these instructions may cause
radio interference. It has been tested and found to comply
with the limits of a Class A computing device as defined
by FCC (Federal Colmnunications Colmnission, U.S.A.)
regulations, Subpart J of Part 15, which are designed to
provide reasonable protection against such interference
when operated in a colrnnercial enviromnent.
This system uses Puron :R:refrigerant (R-410A), which has
higher pressures than R-22 and other refrigerants. No other
refrigerant can be used in this system. Failure to use gage
set, hoses, and recovery systems designed to handle Puron
refrigerant (R-410A) may result in equipment damage or
personal injury. If unsure about equipment, consult the
equipment manufacturer.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300093-01 Printed in U.S.A. Form 30RB-18SI Pg 1 2-12 Replaces: 30RB-17SI
Przeglądanie stron 0
1 2 3 4 5 6 ... 69 70

Podsumowanie treści

Strona 1 - Installation Instructions

AQUASNAP ®30RB060-390Air-Cooled ChillersInstallation InstructionsCONTENTSPageSAFETY CONSIDERATIONS ... 1INTRODUCTION ...

Strona 2

SERVICE AREA 121921480] FROM EACH SIDE OF THE UNIT-- CTSA xCOOLER TUNERVICE AREAl lPDz PBz! f[F CG X188 03]I4R$o, _gN_ol INN03,_IRIRGENTRANCERREACOILG

Strona 3

NOTES:1. Unit must have clearances as follows:Top -- Do not restrict.Sides and End -- 6' from solid surface.2. Temperature relief devices located

Strona 4 - "l ...r

CoSERVICE AREA 1219 2[48 O] FROM EACH SIDE OF THE UNIT r HOD OO ]A=78 i 8765 •m,. ,KAK,_/ .r I _°.i! _O_=_ETX_EAII1°1_ I'1/ 11"1 4F_!-"

Strona 5 - F OOLER'FTU

I#: .I COOLERTUBE!iSERN'BBAREA:6O0OO1[BH H2]PIPING :ENTERANCEAREAIit:l/H OOI IRBHI 123 HB] 123B21 .L ... !IP_N.!ENT_RANC!.AR__EA...

Strona 6 - _'_//' I I".L_

ZSERVICE AREA 12_92140H] FROM EACH SIDE OF THE UNIT7APU¢_ 290880[H440]Ii COOLER TUBESERVICE AREAI--OOOOO[BR6B]H4R!... DDH-GE'VENT"'RG&

Strona 7 - ; II "

SERVICE AREA 121921480] FROM EACH SIDE OF THE UNITIIr_ 14478157001rCOOLER TUBESERVICE AREARSz R9zI I76951[3030]i... 7I IAV &E==CT_ l_///_./_////

Strona 8 - ...<-_j

CONDENSERSENTERING WATER80' VICTAULIC2X 34333 --[13 521WEIGHT CENTER OF GRAVITY_CHX CG_ CGyIb/_9 _M [l_CN] _M lINCH]30RN-160 I0991 3124 _0013_SAI

Strona 9 - A47,[STDI

r SERVICE AREA 1219 2148 O] FRON EACH SIDE OF THE £,NIT! "I!IF! 96040[3F 811I [SERVICE AREIILJ!I|I,iP:IPSz J-- 196374[F7311F--•I... ]A_7 VA\&ap

Strona 10 - .871 ,O NTIN8ROLE

OR,DENSER VE'_T_ONDE_SENIWEIGHT CENTER OF GRAVITY_CHX CG CGyIblk9 H_ [I_CH] MM [I_CH]360A,_90A_ $706 [140_9] [385_]SORD-_90 128S0 3566 _79iA?COOL

Strona 11 - L-9_83s I

I SERVICE AREA 1219 2148 O] FROM EACH SIDE OF THE UNITI"_ I 14478 L_ ...: COOLER TJ ISERVICE_AI[3i 50]POWERBOX 2 _" ...2NOVWRLY ...CI

Strona 12 - 'H_DR'/ L____3D3D_

INTRODUCTIONThese instructions cover installation of 30RB060-390 air-cooled liquid chillers with electronic controls and units withfactory-installed o

Strona 13 - !iSERN'BBAREA

I,OA A_SESERVICEAREA 9219214H0] FROM EACH SIDE OF THE UNIT 990 54 SCALE I: 6I • 3_DA_3 ... 80000_ _"12429 :01 2O 7 3150 = =,I : "'&quo

Strona 14 - H4R!... DDH

I'D• iSERVICE AREA 1219 2148 O] FRO_ EACH SIDE OF THE _,RITIi: r_ZO16SA R:GRDO ,,1, ,1 HGDOD[31 50]j [79 3D] [ 09 53]I .:_.E3D6 .:oH,o:.=,o, . :.

Strona 15 - _1 i' II i'

I,OI,O)WE__ox z BOXiCgT ¢ CET a,aF SERVICE AREA 1219214801 FROM EACH SlgE OF THE UNIT -- 315854[12435]I321054 ... tI [126 40] [31150] / / Lbx14478 _

Strona 16 - .08_1I L

AUCU COIL UNITS WITHOUT PUMP -- ENGLISHUNIT30RBO6OO70O8OO9O100110UNIT30RB120130150160170UNIT30RB19021022525O2753OOUNIT30RBO6OO7OO8OO9O100110UNIT30RB12

Strona 17 - "1 !

AL/CU COIL UNITS WITH SINGLE PUMP -- ENGLISHUNIT30RBO6OO7OO8OO9O100110UNIT30RB120130150160170UNIT30RB190MOUNTING WEIGHT (Ib)Single Pump AI/Cu*A i B i

Strona 18 - -l!

MCHX COIL UNITS WITH SINGLE PUMP -- ENGLISHUNIT30RBO6OO7OO8OO9O100110UNIT30RB120130150160170UNIT30RB190MOUNTING WEIGHT (Ib)Single Pump MCHX**A i . i o

Strona 19 - POW[R BOX I

UNIT30RBO6OO7OO8OO9O100110UNIT30RB120130150160170UNIT30RB190MCHX COIL UNITS WITH HEAT RECLAIM -- ENGLISHMOUNTING WEIGHT (Ib)Heat Reclaim MCHX**A i B i

Strona 20 - I---;::!°:; :LO,.f

,..ERS,OEI TOF UNIT 2.46" [63 mm]BASE RAIL 14.87" [124 mm]5.35" [136 mm]2.56" [65 mm]OUTER SIDEOF UNITBASE RAIL5.12" [130 mm]

Strona 21 - SCROLLING"_RONEE--.II II

Table 3A -- Physical Data, 30RB060-300 -- EnglishUNIT 30RBOPERATING WEIGHT (Ib)*AI-Cu Condenser CoilCu-Cu Condenser CoilMCHX Condenser CoilREFRIGERANT

Strona 22 - "M:oDoSEEDETAIL

Table 3A -- Physical Data, 30RB060-300 -- English (cont)UNIT 30RBOPERATING WEIGHT (Ib)*AI-Cu Condenser CoilCu-Cu Condenser CoilMCHX Condenser CoilREFR

Strona 23 - _l_lclolEIFITota'

30RB - Air-Cooled AquaSnap® ChillerDesign SeriesNominal Sizes060 110 170 275 360*070 120 190 300 390*080 130 210 315"090 150 225 330*100 160 250

Strona 24 - A i B i c i o ITota

Table 3B -- Physical Data, 30RB060-300 -- SIUNIT 30RBOPERATING WEIGHT (kg)*AI-Cu Condenser CoilCu-Cu Condenser CoilMCHX Condenser CoilREFRIGERANT TYPE

Strona 25 - I 1498 I 1743 I 1457 I 5949

Table 3B -- Physical Data, 30RB060-300 -- SI (cont)UNIT 30RBOPERATING WEIGHT (kg)*AI-Cu Condenser CoilCu-Cu Condenser CoilMCHX Condenser CoilREFRIGERA

Strona 26

Table 4A- Physical Data- 30RB315-390- EnglishUNIT 30RBOPERATING WEIGHT (Module A/Module B, Ib)*AI-Cu Condenser CoilCu-Cu Condenser CoilMCHX Condenser

Strona 27 - ,..ERS,OEI T

Table 4B -- Physical Data -- 30RB315-390 -- SIUNIT 30RBOPERATING WEIGHT (Module A/Module B, kg)*AI-Cu Condenser CoilCu-Cu Condenser CoilMCHX Condenser

Strona 28 - 90/41/-Ilt2/41/-I 69/69/-I

13' MINIMUM(3982mm)SIDEAICAUTION- NOTICE TO RIGGERS:ALL PANELS MUST BE IN PLACE WHENRIGGING, DO NOT ATTEMPT TO FORK THESE UNITS IF NO SKID IS SUP

Strona 29 - 162JlOOJ1162J133J1162J162JI

A2A4SIDECAUTION- NOTICE TO RIGGERS:ALL PANELS MUST BE IN PLACE WHEN RIGGING, DO NOT ATTEMPT TO FORK THESE UNITS IF NO SKID IS SUPPLIED,NOTES:. 50 DIA,

Strona 30 - I19119119

Step 2 E Remove Compressor Rack HolddownBolts E The 30RB units are shipped with holddown boltssecuring the compressor rail assembly to the unit base f

Strona 31 - 589158915891-1-1--I

Thecombinationvalveperformsthefollowingfunctions:• Drip-tightshut-offvalve• Springclosuredesignwithanon-slamcheckvalve• Flow-throttlingvalveRefertoFig

Strona 32 - 14 I 14 I I 15 I 16

-'VVV'--Heater (Optional)INSIDEUNITOUTSIDEUNITChilledWater OutHYDRONIC PUMP PACKAGE,),)HeaterChilledWater InLEGENDD -- Drain,3/4-in. NPTD&ap

Strona 33 - 6J4i 6J4i 6J6

condenserflowswitch,temperaturesensorsandrefrigerationdevicestoallowupto 100%ofthecondenserheattobere-claimedforhotwater.Thismeansthatthiswater-cooled

Strona 34 - CAUTION- NOTICE TO RIGGERS:

4:_NOTES:1.2.3.4.LUnit must have clearances as follows:Top -- Do not restrict.Sides and End -- 6' from solid surface.All pumps have drains locate

Strona 35

NOTE: Locate the 3-way valve as close as possible to thechiller to minimize head pressure control response time.SUPPLY _RETURNMODULATING 3-WAYCONTROL

Strona 36

III÷IF-I÷IIL"p,,'=1,=1©©©Master ChillerH©©©4Dual ChillerLWT Sensorsand WellsSlave Chiller©©©_o?llolht ieck ValveI©©© ,i ControlPump and Chec

Strona 37 - AXCAUTION

LDistribution Pump____@ExpansionAir Separatorwith Vent©Ncq co© ©NOTE: Expansion tanks for 3ORB hydronic kits must be installed for chillers piped in p

Strona 38 - -'VVV'

SYSTEMi POT FEEDER ANDAGENT _TEMPORARY i 3ORB UNITPUMP i |\q_¥TO DRAINFig. 37 -- Typical Set Up for Cleaning ProcessSYSTEM I| [ POT FEEDER AND[ DILUTE

Strona 39 - "LX "

Table 6 1 Pump Impeller SizesUNIT PUMP SINGLE PUMP30RB Hp Option Code* Rpm Impeller Dia. (in.)3 O,F 1750 6.55 1,G 1750 7.3060070 7.5 2,H 1750 8.1510 3

Strona 40

Head Pressure(m) ft of fluid(45.7) 150(36.6) 120(27.4) 90(18.3) 60(9.1) 30(o.o) o0(o.oo), , , , , , , ,i i i i i i i i... RPM..., , , , , , 1-

Strona 41 - Fig. 35 -- Tank Baffling

Head Pressure(m) ft of fluid(45.7) 150(36.6) 120(27.4) 90(18.3) 60(9.1) 30(o.o)o0i i i ii i i ii i i i! _ i_ !i i i ii i i ii i i i-6_:1_3in-1-- -42 T

Strona 42 - Reclaim Loop

Head Pressure(m) ft of fluid(45.7) 150(36.6) 120(27.4) 90(18.3) 60(9.1) 30(o.o) o0(o.oo)i i i i i i ii i i i i i i__.*,___,2___dL -'. "_ [ _

Strona 43 - FILTERII I g

Head Pressure(m) ft of fluid(45.7) 150(36.6) 120(27.4) 90(18.3) 60(9.1) 30(o.o) o0iii!ii i i i i i ii i i i i i ii 55 i i i i i ii i 66 i i i i i_11_

Strona 44 - ,_:_,i---_,_,--__X- , , _

Aftertrilmning,theimpellerMUSTbebalanced.Failuretobalancetrilnmedhnpellerscanresultin excessivevibra-tion,noise,andprematurebearingfailure.Impellertrh

Strona 45 -

NOTES:1. Unit must have clearances as follows:Top -- Do not restrict.Sides and End -- 6' from solid sur-face.2. All pumps have drains located at

Strona 46 - ...

PREPARATIONFORYEARROUNDOPERATION-- Iftheunitis in operationyear-round,addsufficientsuitableinhibitedantifreezesolutionsuchaspropyleneor ethyleneglycol

Strona 47 - (m) ft of fluid

60HEAT RECLAIM VESSEL PRESSURE DROP CURVES30RB 60-110 TON5040302010o0.00100 200 300 400 500 600GPM6.31 12.62 18.93 25.24 31.55 37.85L/sFig. 50- 30RB06

Strona 48 - . ; ,, ,--..< ,

Crossbreakthesefaces.Hemthese3edgesbothtopandbottom.1880 [74.0]See Detail A180 [7.0]305 [12.0]POSITION I BAFFLE HEIGHT (X)Control/Power End I 635 [25.

Strona 49 - 81 0130

5. Unitswiththeheatreclaimoptionaresuppliedwithaheaterto protectthereclahncondenserdownto 0° F(-18C).If theunitcontrolstheheatreclahncirculatorpumpand

Strona 50 - / / /11,12013

Proper rotation of condenser fan(s) and pump(s) MUST beverified before pumps or compressors are started. Consultthe Controls, Start-Up and Operation g

Strona 51 - 30RB 120-190 TON

NOTES:I FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS FIELD MODIFICATIONSOR ADBITIOBS MUST BE IN COMPLIANCE WITH ALL APPLICABLE CODES2 WIRING

Strona 52 - Hemthese3edgesbothtop

HEAT RECOVERY BOARD (HRB)_z _ -_ _i/TB7I II(-) I (+)1CONDENSER0-10 V DCWATER VALVEOUTPUTLIIIIIIILEGENDField Control WiringFactory Installed WiringIT11

Strona 53

DUAL CHILLER CONTROL OPTION-- If the Dual Chilleralgorithm is used and the machines are installed in parallel, anadditional chilled water sensor must

Strona 54

Table 10- 30RB Electrical Data- Single Point UnitsUNIT 30RBO6O07008O090100110120130150160170190210225250275300UNIT VOLTAGESuppliedV-Hz (3 Ph) Min Max2

Strona 55 - NON-FUSED DISCONNECT

Table 10 -- 30RB Electrical Data -- Single Point Units (cont)UNIT VOLTAGEUNIT 30RB SuppliedV-Hz (3 Ph) Min Max208/230-60 187 253360-60 342 418A 460-60

Strona 56 - _z _ -_ _

Q'hNOTES:1. Unit must have clearances as follows:Top -- Do not restrict.Sides and End -- 6' from solid surface.2. Temperature relief devices

Strona 57 - (Part No. 30RB660036)

Table 10 -- 3ORB Electrical Data -- Single Point Units (cont)UNIT 30RB060O70O80090100110120130150160170190UNIT VOLTAGESuppliedV-Hz(3 Ph) Min Max208/23

Strona 58 - 6_.2 _o 8_.6 _o - -

Table 11 -- 30RB Electrical Data -- Dual Point Units30RBUNIT SIZE060070UNIT VOLTAGE NO HYDRONIC PACKAGE 3 HP PUMP, 1750 RPM 5 HP PUMP, 1750 RPMV-Hz Su

Strona 59 - XL XL XL Size

Table 11 -- 30RB Electrical Data -- Dual Point Units (cont)UNIT VOLTAGE30RB Supplied MCAUNIT SIZE V-Hz (3 Ph)Min Max XL208/230-60 187 253 5198/2438380

Strona 60

Table 11 -- 30RB Electrical Data -- Dual Point Units (cont)30RB UNIT VOLTAGE 7.5 HP PUMP,UNIT Supplied MCA MOCPSIZE V-Hz(3 Ph) Min Max XL XL208/230-60

Strona 61

Table 12 -- Condenser Fan Electrical DataUNIT UNIT VOLTAGE STANDARD CONDENSER FANS30RB V-Hz (3 Ph) Circuit A Quantity FLA (each) Circuit B Quantity FL

Strona 62 - MCA MOCP ICF Rec

UNIT30RB060070O8009O10011012O130150160, 315A, 315B, 330B170, 330A, 345A, 345B, 360B190, 360A, 390A, 390B210225250275300LEGENDLRA -- Locked Rotor AmpsR

Strona 63

CARRIER COMFORT NETWORK :R:(CCN) COMMUNICA-TION BUS WIRING--The communication bus wiring is ashielded, 3-conductor cable with drain wire and is field

Strona 64

UNIT SECURITY/PROTECTION ACCESSORIES -- Forapplications with unique security and/or protection require-ments, several options are available for unit p

Strona 65

BT485TERMINATORBACNETCONNECTION(BAS PORT)Txl LED IRxl LED I1 ®I ®I ®I ®/I ®II ®Tx2 LED ---------Rx2 LEDEIA-485JUMPERS I i_IOPN-UPCn/cn/cSignalGround24

Strona 66 - Fig. 57 -- TB-3 -- CCN Wiring

®BACnet_CRet MSFPAWGCL2PDCFEPNECO.D.TCULFig. 60 -- BT485 Terminator InstallationTable 16- MS/TP Wiring RecommendationsSPECIFICATION RECOMMMENDATIONCab

Strona 67 - Refrigerant Circuit

--4SERVICE AREA 1219 2148 O] FROM EACH SIDE OF THE UNIT: _-- ----"T1017 46[40 06]CG xe, CGy... i 223608i _ i_ I 188031788353104]163207 7 5516425

Strona 68 - I[,, I... I

Copyright 2012 Carrier CorporationManufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and

Strona 69 - Wire and Cable

Go_ iA4781570]COOLER TUBESERVICE AREALL_PDz PS zSERVICE AREA i219 2148 O] FROM EACH SIDE OF THE UNITCG X...<-_j,22484 -[885]"1rOe ¸- ]-¢i_ __O

Strona 70

NOTES:1. Unit must have clearances as follows:Top -- Do not restrict.Sides and End -- 6' from solid surface.2. Temperature relief devices located