ELECTRONIC PROTECTION RELAY (EPR) On Cutler-
Hammer solid state starters, the EPR is designed to provide
an alternative to conventional motor protection due to over-
current. See Fig. 53. It performs the following functions:
Test Button The TEST button provides testing of the EPR’s
ability to detect overload, test relay operation, and simulate
motor load.
System Ready (SYST RDY) This light-emitting diode (LED)
provides a visual indication that the EPR is
functioning.
Trip Time Potentiometer The Trip Time potentiometer has
50 selectable overload trip classes ranging from 1 to
50 seconds.
Reset Time Potentiometer The Reset Time potentiometer
has 5 to 120 minutes of motor cooling reset.
Full Load Amperes (FLA) The FLA potentiometer is ad-
justable from 1 to 1,500 amps, based on overload frame size.
Trip LED The Trip LED provides a visual indication that
the EPR has detected an overload condition and tripped.
Fault (FLT) LED The FLT LED is an indicator light.
Reset Button The RESET button allows for the manual
reset of the EPR.
Trip, Common (COM), and FLATest Terminals The Trip,
COM, and FLA test terminals provide for Digital Voltmeter
(DVM) calibration.
Terminal 1 (TB1) Terminal 1 is the 120 vac connection
to power the EPR.
Terminal 4 (TB4) Terminal 4 is the normally closed, elec-
tronically isolated EPR contact for overload trip.
NOTE: When the System Ready (SYST RDY) LED is a steady
green light, no fault has been found in the solid-state starter
operation. When the SYST RDY LED is a steady green light
and the fault indicator (FLT) is a flashing red light, the a
motor overload trip is approaching. When the FLT LED is
a solid red light and the SYST RDY LED is a flashing green
light, a motor overload trip has occurred. When the FLT LED
is a solid red light and the SYST RDY LED is a solid green
light, the overload has tripped because of a phase unbalance.
Fig. 50 Resistance Check
SCR Silicon Control Rectifier
Fig. 51 SCR and Power Poles
SCR Silicon Control Rectifier
Fig. 52 Typical Cutler-HammerT Solid-State Starter
(Internal View)
FLT Fault LED
Fig. 53 Cutler-Hammer Terminal Functions
84