UNIT START-UP CHECKLIST
MODEL NO.: SERIAL NO.:
DATE: TECHNICIAN:
I. PRE-START-UP:
[] VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
[] VERIFY INSTALLATION OF OUTDOOR AIR HOOD
[] VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
[] VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
[] CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE
[] CHECK THAT OUTDOOR AIR INLET SCREENS ARE IN PLACE
[] VERIFY THAT UNIT IS LEVEL
[] CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SETSCREW
IS TIGHT
[] VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
[] VERIFY THAT SCROLL COMPRESSORS ARE ROTATING IN THE CORRECT DIRECTION
[] VERIFY INSTALLATION OF THERMOSTAT
[] VERIFY THAT CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR AT LEAST 24 HOURS
II. START-U P
ELECTRICAL
SUPPLY VOLTAGE Ll-L2 L2-L3 L3-Ll
COMPRESSOR AMPS COMPRESSOR A 1
ELECTRIC HEAT AMPS (IF EQUIPPED)
SUPPLY FAN AMPS
LI L2 L3
LI L2 L3
LI L2 L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
ELECTRIC HEAT SUPPLY AIR
PRESSURES
F DB (Dry Bulb)
FDB
F
F
F WB (Wet Bulb)
REFRIGERANT SUCTION CIRCUIT A PSIG
REFRIGERANT DISCHARGE CIRCUIT A PSIG
[] VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGES 41 AND 42
GENERAL
[] ECONOMIZER MINIMUM VENT AND CHANGEOVER SETFINGS TO JOB REQUIREMENTS
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 14 PC 111 Catalog No. 535-00139 Printed in U.S,A. Form 50PG-5SI PO CL-1 8-05 Replaces: New