Table 2B -- Electrical Data -- Units With Optional Convenience Outlet (cont)
UNIT
50PG
05
(cont)
VOLTAGE COMPRESSOR OFM
NOMINAL RANGE FLA IFM
POWER SUPPLY
FLA FLA
Volte-Ph-Hz Min Max RLA LRA Qty (ea)
5.2
208/230-3-60 187 283 14.6 91 1 1.0
4,9
2,6
460-3-60 414 506 7.1 46 1 0.5
2,1
POWER ELECTRIC HEAT
EXHAUST IFM
FLA TYPE Nominal
(ea) FLA kW*
10.0/11.5 3.8/ 8.0
4.9 -- STD 15.0/17.3 5.6/ 7.5
20,0/23.1 7.5/10,0
30.0/34.6 11.3/18.0
40.0/46.2 15.0/20.0
10,0/11.5 3,8/ 5,0
15,0/17.3 8,6/ 7,5
-- ALT 20.0/23.1 7.5/10.0
30.0/34.6 11.3/18.0
40.0/46.2 15.0/20.0
10,0/11.5 3,8/ 8,0
15,0/17.3 5,6/ 7,5
1.4 STD 20.0/23.1 7.5/10.0
30,0/34,6 11,3/15.0
40.0/46.2 15.0/20.0
10,0/11.5 3,8/ 8,0
15,0/17.3 5,6/ 7,8
5.2 1.4 ALT 20.0/23.1 7.8/10.0
30.0/34.6 11.3/15.0
40.0/46.2 15.0/20.0
5,8 5,0
2,1 -- STD 8,7 7,5
11,5 10,0
17,3 15,0
23,1 20,0
5,8 5,0
-- ALT 8,7 7,5
11,8 10,0
17,3 15.0
23,1 20,0
5.8 5,0
0.6 STD 8.7 7,8
11,8 10,0
17,3 15,0
23,1 20,0
5.8 5,0
2,6 0.6 ALT 8,7 7,5
11,5 10,0
17,3 15,0
23,1 20,0
POWER SUPPLY DISCONNECT
SIZE
MCA MOCPt FLA LRA
29.0/29.0 30/30 29/29 110/110
29.0/29.0 30/30 29/29 110/110
30.9/33.8 35/35 29/31 110/110
37.1/41.0 40/45 34/38 110/110
49.6/88,4 80/60 46/51 110/110
62.1/69.9 70/70 57/64 110/110
29.3/29.3 30/30 29/29 128/128
29.3/29.3 30/30 29/29 128/128
31.3/34.1 35/35 29/31 128/128
37.5/41.4 40/45 35/38 128/128
50.0/55.8 60/60 46/81 128/128
62.5/70.3 70/80 58/65 128/128
30.4/30.4 35/35 31/31 112/112
30.4/30.4 35/35 31/31 112/112
32.6/35.8 35/40 31/33 112/112
38.9/42.8 40/48 36/39 112/112
81.4/57.1 60/60 47/83 112/112
63.9/71.6 70/80 89/66 112/112
30.7/30.7 35/35 31/31 130/130
30.7/30.7 35/35 31/31 130/130
33.0/35.9 35/40 31/33 130/130
39.3/43.1 40/48 36/40 130/130
81.8/57.8 60/60 48/83 130/130
64.3/72.0 70/80 59/66 130/130
13,7 15 14 88
13.7 15 14 55
16,3 20 15 58
19,8 20 18 55
27,0 30 28 55
34.3 35 32 55
14.2 15 14 64
14.2 15 14 64
16.9 20 16 64
20.4 28 19 64
27.6 30 25 64
34.9 35 32 64
14,3 15 14 56
14,3 15 14 56
17.0 20 16 56
20,5 28 19 56
27.8 30 26 56
35,0 40 32 56
14,8 15 15 68
14,8 15 15 68
17.6 20 16 65
21.1 25 19 65
28.4 30 26 65
35,6 40 33 65
LEGEND
FLA -- Full Load Amps
NACR -- Heating, Air Conditioning and Refrigeration
IFM -- Indoor (Evaporator) Fan Motor
LRA -- Locked Rotor Amps
MCA -- Minimum Circuit Amps
MOCP -- Maximum Overcurrent Protection
NEC -- National Electrical Code
OFM -- Outdoor (Condenser) Fan Motor
RLA -- Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v or
600 v. If power distribution voltage to unit varies from rated heater voltage,
heater kW will vary accordingly.
l-Fuse or HACR circuit breaker,
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be
fuse or circuit breaker,
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of
voltage imbalance,
% Voltage Imbalance
= 100 x max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60.
A B c AB = 224v
BC = 231 v
AC = 226 v
Average Voltage -
224 + 231 + 226
3
681
=--
3
= 227
Determine maximum deviation from average voltage.
(AB) 227 - 224 = 3 v
(BC) 231 - 227 = 4 v
(AC) 227 - 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
4
% Voltage Imbalance = 100 x 22"_-
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
I IMPORTANT: If the supply voltage phase imbalance is more than 2%, 1
contact the local electric utility company immediately.
l
]8