19
I
18 %'*_ LEDON
17
16- -- - LED OFF
15
<
E14
13
12
11
10
9
40 45 50
LED ON
55 60 65 70 75 80
DEGREES FAHRENHEIT
Fig. 15 -- Temperature Changeover Set Points
/
--m,
TRD --
i
5
-
4
EF B
EF1
Fig. 16 -- EconoMi$er IV Control
EXHAUST
FAN SET POINT
LED LIGHTS
WHEN EXHAUST
CONTACT iS MADE
MINIMUM DAMPER
POSITION SETTING
MAXIMUM DAMPER
DEMAND CONTROL
VENTILATION SET POINT
LED LIGHTS WHEN
DEMAND CONTROL
VENTILATION INPUT
iS ABOVE SET POINT
DEMAND CONTROL
VENTILATION SET POINT
LED LIGHTS WHEN
OUTDOOR AiR iS
----x (
SUITABLE FOR
FREE COOLING
ENTHALPY
CHANGEOVER SET POINT
Fig. 17 -- EconoMi$er IV Controller Potentiometer
and LED Locations
Indoor Air Quality (IAQ) Sensor Input -- The IAQ input
can be used for demand control ventilation control based on the
level of CO2 measured in the space or return air duct.
Mount the optional IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and
AQI terminals of the controller Adjust the DCV potentiome-
ters to correspond to the DCV voltage output of the indoor air
quCdity sensor at the user-determined set point. See Fig. 19.
If a separate field-supplied transformer is used to power the
IAQ sensor, the sensor must not be grounded or the
EconoMiSer [V control board will be &_maged. See Fig. 14.
Power Exhaust -- The factory-installed power exhaust will be
factory wired and installed. [f an accessory power exhaust is to
be installed, see the accessory power exhaust installation in-
structions included with the power exhaust for inst_dlation and
wiring. The wiring plug on the power exhaust is connected to
wiring harness plug PLI-3,4.
Exhaust Set Point Adjustment -- The exhaust set point will
determine when the exhaust fan runs based on damper position
(if accessory power exhaust is installed). The set point is modi-
fied with the Exhaust Fan Set Point (EXH SET) potentiometer.
The set point represents the &Lmper position above which the
exhaust fans will be turned on. When there is a call for exhaust,
the EconoMi$er IV controller provides a 45 _+15 second delay
before exhaust fan activation to allow the dampers to open.
This delay allows the damper to reach the appropriate position
to avoid unnecessary fan overload.
Minimum Position Control -- There is a minimum damper
position potentiometer on the EconoMiSer IV controllel: See
Fig. 17. The minimum dmnper position maintains the mini-
mum airflow into the building during the occupied period.
When using demand ventilation, the minimum &tmper po-
sition represents the minimum ventilation position for VOC
(volatile organic compounds) ventilation requirements. The
maximum demand ventilation position is used for fully occu-
pied ventilation.
When demand ventilation control is not being used, the
minimum position potentiometer should be used to set the
occupied ventilation position. The maximum demand ventila-
tion position should be turned lully clockwise.
Adjust the minimum position potentiometer to _dlow the
minimum amount of outdoor air, as required by local codes, to
enter the building. Make minimum position adjustments with
at least 10° F temperature difference between the outdoor and
return-air temperatures.
To determine the minimum position setting, perform the
following procedure:
1. Calculate the appropriate mixed air temperature using the
following formula:
(To x OA) + (TR x RA) = TM
To = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Mixed-Air Temperature
As an example, if local codes require 10% outdoor air
during occupied conditions, outdoor-air temperature is
60 K and return-air temperature is 75 IF.
(60 x. 10) + (75 x .90) = 73.5 F
2. Disconnect the mixed air sensor fiom terminals T and TI.
3. Ensure that the factory-installed jumper is in place across
terminals P and PI. If remote &_mper positioning is being
used, make sure that the terminals are wired according to
Fig. 14 and that the minimum position potentiometer is
turned fully clockwise.
24