Carrier 50PG03-07 Dokumentacja Strona 40

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 39
MOTOR
MOUNTING
BASE
SCREW
(HIDDEN)
FAN DECK
STOP
Refrigerant Charge -- Amount of refrigerant charge is
listed on unit nameplate. Refer to Carder GTAC II; Module 5;
Charging, Recovery. Recycling, and Reclmnation section for
chmging methods and procedures. Unit panels must be in place
when unit is operating dunng charging procedure.
Puron® (R-410A) refrigerant cylindel_ contain a dip tube
which _dlows liquid refrigerant to flow from the cylinder in an
upright position. Charge units with cylinder in the upright posi-
tion and a commerci_d type metering device in the manifold hose.
FAN
MOTOR PULLEY
PULLEY
SCREW
SLIDE-OUT
PAN DECK
Fig. 22 -- Evaporator-Fan Motor Adjustment
STRAIGHTEDGE MUST
PARALLEL
WITH BELT
PULLEY
PULLEY
MOTOR AND FAN
SHAFTS MUST BE
PARALLEL
MOVABLE
FLANGES
SETSCREWS_
FIXED FLANGES
SINGLE-GROOVE
This system uses Puron refrigerant which has higher
pressures than R-22 and other refrigerants. No other refrig-
erant may be used in this system. Gage set, hoses, and
recovery system must be designed to handle Puron refrig-
erant. If unsure about equipment, consult the equipment
manu factureE
NOTE: Do not use recycled refrigerant as it may contain
contaminants.
NO CHARGE -- Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refriger-
ant Qefer to unit nameplate).
LOW CHARGE COOLING -- Using cooling charging chart
(see Fig. 26-30), add or lemove refrigerant until conditions of
the chart are met. An accurate pressure gage and temperature-
sensing device is lequiled. Charging is accomplished by
ensuring the proper amount of liquid subcooling. Connect
pressure gage to the compressor discharge service v_dve.
Connect temperature sensing device to the liquid line between
the condenser and the TXV (thermostatic expansion valve) and
insulate it so that ambient temperature does not affect reading.
TO USE THE COOLING CHARGING CHART -- Use the
above temperature and pressure readings, and find the intersec-
tion point on the cooling charging chart. If intersection point on
chmt is above line, add refrigerant. If intersection point on
chmt is below line, carefully recover some of the charge. Re-
check suction pressure as charge is adjusted.
NOTE: Indoor-air cfm must be within normal operating range
of unit. All outdoor fans must be operating.
The TXV is set to maintain between 10 and 15 degrees of
superheat at the compressors. The valves are factory set and
cannot be adjusted. Do not use a TXV designed for use with
R-22 refrigemnt.
Fig. 23 -- Evaporator-Fan Alignment and
Adjustment
Fig. 24 -- Condenser-Fan Adjustment
5OOO
4500
4000
3500
3000
2500
2000
1500
1000
500
LEAK IN
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
0 1 2 3 4 5 6 7
MINUTES
Fig. 25 -- Deep Vacuum Graph
4O
Przeglądanie stron 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 48 49

Komentarze do niniejszej Instrukcji

Brak uwag