25
-Check that the wheel is rotating in the correct direc-
tion.This is indicated by an arrow on the casing.
-Check if the wheel seals are fitting correctly.
-Check if belt tension is correct.
-Check if the motor and the rotation monitor have
been correctly connected.
-Check if the controller has been correctly connected
and set in accordance with the instructions of the
supplier.
-Check if the rotor speed has been set correctly.
-The following warning pictogram is attached to the
panel:rotating parts.
Used if dampers are installed.
-Check if the actuator motor has been installed in
accordance with the instructions of the supplier.
-Check if the correct angle has been set.
-Check the fixing of the steam pipe.
-Check the steam supply and condensate drain pipes.
-For longer pipes install an extra condensate pan in
accordance with the instructions of the supplier.
-Check if the pollution trap has been installed.
-The condensate drain should not be without pressure
in accordance with the manufacturer’s instructions.
Refer to the instructions of the supplier.
-If the AHU has negative pressure, install a special
siphon ahead of the condensate drain.
-Before starting up the steam humidifier steam
must be introduced slowly into the system to bring
the humidifier to the correct operating temperature.
Once the condensate pipe has reached the operat-
ing temperature, start the actuator motor electrically
or pneumatically and set the desired humidity level.
Refer to the instructions of the supplier.
-A few days after starting up the unit clean the sieve
of the pollution trap and check the condensate drain.
For casings with negative pressure the operation of
the negative pressure system must be controlled with
the check valve.
-Check the fixing of the steam generator.
-Check the steam supply and condensate drain
pipes.
-The condensate drain should not be without pressure
in accordance with the manufacturer’s instructions.
Refer to the instructions of the supplier.
-If the AHU has negative pressure, install a special
siphon ahead of the condensate drain.
-Check the voltage and measure the total current
draw.
10.12. Heat Recovery Wheel
1 - SAFETY CONSIDERATIONS
1.1 - General
The 39HQ air handling units (AHUs) has been designed
and manufactured in accordance with the CE machine
directive EN292. In order to guarantee safe operation and
use of the unit, please carefully read and observe the
instructions in this document and pay special attention to
the warnings that apply to this unit. Any modifications in
the design and/or installation of the AHU that are carried
out without discussion with Alarko Carrier and
without advance written agreement will result in the loss of
the right to any warranty claims and any claim for injury to
personnel as a result of these modifications.
Maintenance procedures may only be carried out by
qualified personnel.
Heating and cooling elements are manufactured and
supplied in accordance with guidelines of the Pressure
Equipment Directive (PED).
1.2 - Applications
The AHU is designed for the movement and conditioning
of air, unless otherwise agreed during the design stage.
1.3 - Instruction types
The following warning pictograms and labels with text are
used.
Lifting point
This pictogram shows where the AHU must be lifted and is
positioned on the support beam.
Lifting prohibited
This pictogram shows that no horizontal transport devices
must be placed under this frame section, such as pallet
lifters or the forks of fork lift trucks. It is also forbidden to
place lifting devices for transport and storage under this
frame element.
Earthing
This pictogram indicates where the AHU must be earthed
and is on one of the support beams beneath the casing in
the fan section.
- The electrical components in the AHU must be earthed,
except for components with double insulation and/or
components with a supply voltage below 50 V.
- The electrical components must be installed in accordance
with national and local regulations.
Rotating parts
This pictogram indicates that there are rotating parts behind
this access cover, door or panel which may cause injury. The
components that include rotating parts are the fan and heat
recovery wheel. If there are special customer-specific
components behind doors, access covers or panels that
include rotating parts and pose a potential risk, this is also
indicated by this pictogram.
Hot surfaces
This pictogram indicates that there are components behind
this access cover, door or panel that can cause serious burns
when touched.
The components that may have hot surfaces are the steam
humidifier, steam heater and the electric heater. If there are
special special customer-specific components behind doors,
access covers or panels that have hot surfaces and pose a
potential risk, this is also indicated by this pictogram.
4
10.13. Plate Heat Exchanger
-Check if the dampers close correctly.
-Check if the damper can open to the correct position.
-Check operation after the power has been restored
following a power cut. Some dampers must be open,
others must be closed.
-Check if fins have been bent during transport. Correctly
straighten the fins.
-Check if the siphon has been correctly installed. Check
if siphon cover and ball have been correctly installed.
10.14. Direct Steam Humidification
1 - SAFETY CONSIDERATIONS
1.1 - General
The 39HQ air handling units (AHUs) has been designed
and manufactured in accordance with the CE machine
directive EN292. In order to guarantee safe operation and
use of the unit, please carefully read and observe the
instructions in this document and pay special attention to
the warnings that apply to this unit. Any modifications in
the design and/or installation of the AHU that are carried
out without discussion with Alarko Carrier and
without advance written agreement will result in the loss of
the right to any warranty claims and any claim for injury to
personnel as a result of these modifications.
Maintenance procedures may only be carried out by
qualified personnel.
Heating and cooling elements are manufactured and
supplied in accordance with guidelines of the Pressure
Equipment Directive (PED).
1.2 - Applications
The AHU is designed for the movement and conditioning
of air, unless otherwise agreed during the design stage.
1.3 - Instruction types
The following warning pictograms and labels with text are
used.
Lifting point
This pictogram shows where the AHU must be lifted and is
positioned on the support beam.
Lifting prohibited
This pictogram shows that no horizontal transport devices
must be placed under this frame section, such as pallet
lifters or the forks of fork lift trucks. It is also forbidden to
place lifting devices for transport and storage under this
frame element.
Earthing
This pictogram indicates where the AHU must be earthed
and is on one of the support beams beneath the casing in
the fan section.
- The electrical components in the AHU must be earthed,
except for components with double insulation and/or
components with a supply voltage below 50 V.
- The electrical components must be installed in accordance
with national and local regulations.
Rotating parts
This pictogram indicates that there are rotating parts behind
this access cover, door or panel which may cause injury. The
components that include rotating parts are the fan and heat
recovery wheel. If there are special customer-specific
components behind doors, access covers or panels that
include rotating parts and pose a potential risk, this is also
indicated by this pictogram.
Hot surfaces
This pictogram indicates that there are components behind
this access cover, door or panel that can cause serious burns
when touched.
The components that may have hot surfaces are the steam
humidifier, steam heater and the electric heater. If there are
special special customer-specific components behind doors,
access covers or panels that have hot surfaces and pose a
potential risk, this is also indicated by this pictogram.
4
10.15. Electrical Steam Humidification
-The following warning pictogram is attached to the
panel:hot surface.
1 - SAFETY CONSIDERATIONS
1.1 - General
The 39HQ air handling units (AHUs) has been designed
and manufactured in accordance with the CE machine
directive EN292. In order to guarantee safe operation and
use of the unit, please carefully read and observe the
instructions in this document and pay special attention to
the warnings that apply to this unit. Any modifications in
the design and/or installation of the AHU that are carried
out without discussion with Alarko Carrier and
without advance written agreement will result in the loss of
the right to any warranty claims and any claim for injury to
personnel as a result of these modifications.
Maintenance procedures may only be carried out by
qualified personnel.
Heating and cooling elements are manufactured and
supplied in accordance with guidelines of the Pressure
Equipment Directive (PED).
1.2 - Applications
The AHU is designed for the movement and conditioning
of air, unless otherwise agreed during the design stage.
1.3 - Instruction types
The following warning pictograms and labels with text are
used.
Lifting point
This pictogram shows where the AHU must be lifted and is
positioned on the support beam.
Lifting prohibited
This pictogram shows that no horizontal transport devices
must be placed under this frame section, such as pallet
lifters or the forks of fork lift trucks. It is also forbidden to
place lifting devices for transport and storage under this
frame element.
Earthing
This pictogram indicates where the AHU must be earthed
and is on one of the support beams beneath the casing in
the fan section.
- The electrical components in the AHU must be earthed,
except for components with double insulation and/or
components with a supply voltage below 50 V.
- The electrical components must be installed in accordance
with national and local regulations.
Rotating parts
This pictogram indicates that there are rotating parts behind
this access cover, door or panel which may cause injury. The
components that include rotating parts are the fan and heat
recovery wheel. If there are special customer-specific
components behind doors, access covers or panels that
include rotating parts and pose a potential risk, this is also
indicated by this pictogram.
Hot surfaces
This pictogram indicates that there are components behind
this access cover, door or panel that can cause serious burns
when touched.
The components that may have hot surfaces are the steam
humidifier, steam heater and the electric heater. If there are
special special customer-specific components behind doors,
access covers or panels that have hot surfaces and pose a
potential risk, this is also indicated by this pictogram.
4
-If a cooling coil is incorporated, after several days
of cooling operation check the condensate drain and
operation of the plastic siphon. If necessary clean
the siphon.