Carrier XRV Dokumentacja Strona 69

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 190
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 68
69
VERIFY VFD CONFIGURATION AND CHANGE
PARAMETERS IF NECESSARY (Fig. 35)
VFD CHILLER FIELD SET UP AND VERIFICATION
Label Locations
— Verify that the following labels have been
installed properly and match the chiller requisition:
Surge Parameters — Located inside the control panel. See
Fig. 10.
Refrigeration Machine Nameplate — Located on the right
side of the control panel. See Fig. 10.
External Machine Electrical Data Nameplate — Located on
the right side of the VFD as viewed from its front. See
Fig. 35.
Internal Machine Electrical Data Nameplate — Located on
the inside of the left VFD enclosure door. See Fig. 35.
Record all nameplate information on the Initial Start-up
Checklist at the end of this manual.
Check VFD_CONFIG TABLE
— Enter the VFD_CONF
screen on the ICVC by entering the following screen
sequence when the chiller is not running:
•MENU
•SERVICE
Password (default 1111)
•VFD CONFIG DATA
Password (default 4444)
VFD_CONF
Confirm that the following parameters in the
VFD_CONF screen match the values on the Internal
Machine Electrical Data Nameplate:
Motor Nameplate Voltage — Voltage required to run at
motor rating.
Compressor 100% Speed — Compressor speed required to
run at chiller design point.
Rated Line Voltage — Nominal line voltage selected for the
job site.
Rated Line Amps — Line current required for the chiller to
run at the design point.
Rated Line Kilowatts — Line power required for the chiller
to run at the design point.
Motor Rated Load kW — Power consumed by the motor
when running at the chiller design point.
Motor Rated Load Amps — Motor current required for the
chiller to run at the design point.
Motor Nameplate Amps — Motor nameplate full load
amps.
Motor Nameplate RPM — Rated speed of the motor when
running at motor nameplate rated frequency, rated current,
and rated voltage.
Motor Nameplate kW — Motor nameplate rated power.
Inverter PWM Frequency — Sets the carrier frequency for
the pulse width modulation output.
NOTE: Other parameters on these screens are normally left at
the default settings; however, they may be changed by the
operator as required. The voltage and current imbalance level
and imbalance persistence time on the VFD_CONF table can
be adjusted to increase or decrease the sensitivity of these fault
conditions. Increasing time or persistence decreases sensitivity.
Decreasing time or persistence increases sensitivity to the fault
condition.
NOTE: Some of the parameters can be changed only when the
drive is stopped.
HAND CALCULATE VARIABLE PRIMARY FLOW
(VPF) SURGE PREVENTION CONFIGURATIONS —
The configurations entered determine the Surge Prevention line
that the controls use to raise the speed of the VFD if the com-
pressor operating point nears this line.
Calculate ΔP maximum and ΔP minimum using 2 point
method shown in sections below. If the original selection con-
figuration points are available, use ΔP1 and ΔP4 from that se-
lection as ΔP maximum and ΔP minimum. If the original selec-
tion configuration was for a 2 point surge line, use ΔP1 and
ΔP2.
Use the default values for the following configurations:
Surge / HGBP IGV min. = 5.0
Surge / HGBP IGV max = 100.0
Surge Line Shape Factor = -0.040
Surge Line Speed Factor = 1.85
Surge Line High Offset = 1.0
Surge/ HGBP Deadband = 1
Calculate Maximum Load
— To calculate the maximum load
points, use the design load condition data. If the chiller full load
cooler temperature difference is more than 15 F (8.3 C),
estimate the refrigerant suction and condensing temperatures at
this difference. Use the proper saturated pressure and tempera-
ture for the particular refrigerant used.
Suction Temperature:
42 F (5.6 C) = 37 psig (255 kPa) saturated
refrigerant pressure (HFC-134a)
Condensing Temperature:
98 F (36.7 C) = 120 psig (1827 kPa) saturated
refrigerant pressure (HFC-134a)
IMPORTANT: The VFD controller has been factory con-
figured for use and communications to the International
Chiller Visual Controller (ICVC). Some parameters are
specific to the chiller configuration and will need to be ver-
ified prior to operation. All command functions must be
initiated from the ICVC.
:
Fig. 35 — Machine Electrical Data Nameplate
INTERNAL EXTERNAL
a19-1626
WARNING
It is the operators responsibility to distribute access to the
ICVC passwords. Carrier is not responsible for unauthor-
ized access violations within the operator’s organization.
Failure to observe this warning could result in bodily
injury.
Przeglądanie stron 68
1 2 ... 64 65 66 67 68 69 70 71 72 73 74 ... 189 190

Komentarze do niniejszej Instrukcji

Brak uwag