19XRV PIC III VFD_CONF TABLE CONFIGURATION SHEET
NOTE: Those parameters marked with a * shall not be downloaded to the VFD, but shall be used in other calculations and algorithms in the ICVC.
DESCRIPTION RANGE UNITS DEFAULT VA L U E
Motor Nameplate Voltage 346 to 480 VOLTS 460
Compressor 100% Speed 45.0 to 62.0 Hz 60.0
Line Freq=60 Hz? (No=50) 0/1 NO/YES YES
* Rated Line Voltage 346 to 600 VOLTS 460
* Rated Line Amps 10 to 1500 AMPS 200
* Rated Line Kilowatts 0 to 7200 kW 100
* Motor Rated Load KW 0 to 7200 kW 100
* Motor Rated Load Amps 10 to 1500 AMPS 200
Motor Nameplate Amps 10 to 1500 AMPS 100
Motor Nameplate RPM 1500 to 3600 3456
Motor Nameplate KW 0 to 5600 kW 100
Inverter PWM Frequency
(0=4 k Hz, 1=2 k Hz)
0/1 0
Skip Frequency 1 0.0 to 102.0 Hz 102.0
Skip Frequency 2 0.0 to 102.0 Hz 102.0
Skip Frequency 3 0.0 to 102.0 Hz 102.0
Skip Frequency Band 0.0 to 102.0 Hz 0.0
Line Voltage % Imbalance 1 to 10 % 10
Line Volt Imbalance Time 1 to 10 SEC 10
Line Current % Imbalance 5 to 40 % 40
Line Current Imbal Time 1 to 10 SEC 10
Motor Current % Imbalance 5 to 40 % 40
Motor Current Imbal Time 1 to 10 SEC 10
Increase Ramp Time 5 to 60 SEC 30
Decrease Ramp Time 5 to 60 SEC 30
Single Cycle Dropout 0/1 DSABLE/ENABLE DSABLE