Carrier is participating inthe Eurovent CertificationProgramme. Products areas listed in the EuroventDirectory of CertifiedProducts.50RHE 006-060Water
10Water supply and quantityCheck water supply. Water supply should be plentiful and ofgood quality. See Table 2 for water quality guidelines.IMPORTANT
11Fig. 9 - Typical Aquazone Complete C control wiring (single-phase unit)LegendAL Alarm relay contactsBR Blower relayCAP Compressor capacitorCB Circui
12Fig. 10 - Typical Aquazone Complete C control wiring (three-phase unit)LegendAL Alarm relay contactsBR Blower relayCAP Compressor capacitorCB Circui
13L123456G/YG/YYELREDBLKBLKYELRED BLU6824CRRED* BLU*REDCAPSCRBLK24BR168YELBLKYEL OR WHTBLKBLUREDBMCBRNBR2NO COMNCTRANSBLKRED(220V)ORG(240V)24VCBYELBLU
14Fig. 12 - Typical Aquazone Deluxe D control wiring (three-phase unit)LegendAL Alarm relay contactsBM Blower motorBMC Blower motor capacitorBR Blower
15Table 3 - Electrical data50RHE Power supply Voltage Compressor Fan Total Min. circuit Max.V-ph-Hz min./max. RLA LRA motor unit current fuse/HACRV FL
16CONNECT THE BLUE WIRE TO:FAN MOTORMEDIUM FACTORY SETTINGH FOR HIGH SPEED FANM FOR MEDIUM SPEED FANL FOR LOW SPEED FANHMLBLU3.8.4 - PSC (permanent sp
173.9 - Low voltage wiring (see Fig. 15)3.9.1 - Thermostat connectionsThe thermostat should be wired directly to the Aquazone controlboard (see Figs.
184 - PRE-START-UP4.1 - System checkoutWhen the installation is complete, follow the system checkoutprocedure outlined below before starting up the sy
19Alarm relay setting - Select jumper 4 (JW4-AL2 dry) for con-necting alarm relay terminal (AL2) to 24 VAC (R) or to remainas a dry contact (no connec
2CONTENTS1 - SAFETY CONSIDERATIONS ...
20Cycle with compressor - In this configuration, the relay will beON any time the compressor relay is on.Digital night setback (NSB) - In this configu
216.2 - Scroll compressor rotationIt is important to be certain compressor is rotating in the properdirection. To determine whether or not compressor
22Table 9 - Typical unit operating pressures and temperaturesEntering Water Cooling Heatingwater flow Suction Discharge Super- Sub- Water temp. Air te
236.7 - Anti-freezeIn areas where entering loop temperatures drop below 4.4°C orwhere piping will be routed through areas subject to freezing,anti-fre
247 - OPERATION7.1 - Power up modeThe unit will not operate until all the inputs, terminals andsafety controls are checked for normal operation.NOTE:
258 - SYSTEM TESTSystem testing provides the ability to check the control operation.The control enters a 20-minute test mode by momentarily shor-ting
26Table 15 - Aquazone D control current LED status and alarm relay operationsDescription Status LED Test LED Fault LED Alarm relay(Green) (Yellow) (Re
279.4 - Refrigerant systemVerify air and water flow rates are at proper levels beforeservicing. To maintain sealed circuitry integrity, do not install
286. Compare the subcooling temperature with the normaltemperature listed in Table 9. If the measured liquid linetemperature does not agree with the r
29Table 16 - TroubleshootingFault Heating Cooling Possible cause SolutionMain power problems X X Green status LED Off Check line voltage circuit break
31 - SAFETY CONSIDERATIONSInstallation and servicing of air-conditioning equipment can behazardous due to system pressure and electrical components.On
30Table 16 - Troubleshooting (cont’d)Fault Heating Cooling Possible cause SolutionOnly compressor runs X X Thermostat wiring Check G wiring at heat pu
31Heating cycle analysisCooling cycle analysisHeat of extraction (absorption) or heat of rejection =________ Flow rate (l/s) x ________ Temp. differen
11 - START-UP CHECKLIST - 50RHE R-407C UNITCustomer: ___________________________________ Job name: __________________________________________________M
410. Provide ready access to water valves and fittings, and screw-driver access to unit side panels, discharge collar, and allelectrical connections.1
5Fig. 1 - Dimensions50RHE 006-012 015-024 030 036 042-048 060Overall cabinet mmA (width) 568 568 568 568 568 645B (depth) 1095 1095 1351 1351 1580 180
6Fig. 2 - Typical installation - 50RHE unitsField-supplied transition tominimise pressure lossSupply airInsulated supply duct with atleast one 90° elb
73.3 - Unit locationThe following guidelines should be considered when choosinga location for a water-source heat pump unit:• Units are for indoor use
83.4 - Mounting the unitHorizontal units should be mounted using the factory-installedhangers. Proper attachment of hanging rods to building structure
93.7 - Piping connectionsDepending on the application, there are three types of water-source heat pump piping systems to choose from: water loop,groun