50RHE 006-060
Water-Source Heat Pumps -
Horizontal Units
Installation, Operation and Maintenance Instructions
TM
Przeglądanie stron 0
1 2 3 4 5 6 ... 31 32

Podsumowanie treści

Strona 1 - Horizontal Units

Carrier is participating inthe Eurovent CertificationProgramme. Products areas listed in the EuroventDirectory of CertifiedProducts.50RHE 006-060Water

Strona 2 - CONTENTS

10Water supply and quantityCheck water supply. Water supply should be plentiful and ofgood quality. See Table 2 for water quality guidelines.IMPORTANT

Strona 3

11Fig. 9 - Typical Aquazone Complete C control wiring (single-phase unit)LegendAL Alarm relay contactsBR Blower relayCAP Compressor capacitorCB Circui

Strona 4

12Fig. 10 - Typical Aquazone Complete C control wiring (three-phase unit)LegendAL Alarm relay contactsBR Blower relayCAP Compressor capacitorCB Circui

Strona 5 - Fig. 1 - Dimensions

13L123456G/YG/YYELREDBLKBLKYELRED BLU6824CRRED* BLU*REDCAPSCRBLK24BR168YELBLKYEL OR WHTBLKBLUREDBMCBRNBR2NO COMNCTRANSBLKRED(220V)ORG(240V)24VCBYELBLU

Strona 6

14Fig. 12 - Typical Aquazone Deluxe D control wiring (three-phase unit)LegendAL Alarm relay contactsBM Blower motorBMC Blower motor capacitorBR Blower

Strona 7

15Table 3 - Electrical data50RHE Power supply Voltage Compressor Fan Total Min. circuit Max.V-ph-Hz min./max. RLA LRA motor unit current fuse/HACRV FL

Strona 8 - A 102 mm trap is recommended

16CONNECT THE BLUE WIRE TO:FAN MOTORMEDIUM FACTORY SETTINGH FOR HIGH SPEED FANM FOR MEDIUM SPEED FANL FOR LOW SPEED FANHMLBLU3.8.4 - PSC (permanent sp

Strona 9

173.9 - Low voltage wiring (see Fig. 15)3.9.1 - Thermostat connectionsThe thermostat should be wired directly to the Aquazone controlboard (see Figs.

Strona 10

184 - PRE-START-UP4.1 - System checkoutWhen the installation is complete, follow the system checkoutprocedure outlined below before starting up the sy

Strona 11 - See note 8

19Alarm relay setting - Select jumper 4 (JW4-AL2 dry) for con-necting alarm relay terminal (AL2) to 24 VAC (R) or to remainas a dry contact (no connec

Strona 12

2CONTENTS1 - SAFETY CONSIDERATIONS ...

Strona 13

20Cycle with compressor - In this configuration, the relay will beON any time the compressor relay is on.Digital night setback (NSB) - In this configu

Strona 14 - Fan enable

216.2 - Scroll compressor rotationIt is important to be certain compressor is rotating in the properdirection. To determine whether or not compressor

Strona 15 - Circuit breaker

22Table 9 - Typical unit operating pressures and temperaturesEntering Water Cooling Heatingwater flow Suction Discharge Super- Sub- Water temp. Air te

Strona 16

236.7 - Anti-freezeIn areas where entering loop temperatures drop below 4.4°C orwhere piping will be routed through areas subject to freezing,anti-fre

Strona 17

247 - OPERATION7.1 - Power up modeThe unit will not operate until all the inputs, terminals andsafety controls are checked for normal operation.NOTE:

Strona 18

258 - SYSTEM TESTSystem testing provides the ability to check the control operation.The control enters a 20-minute test mode by momentarily shor-ting

Strona 19

26Table 15 - Aquazone D control current LED status and alarm relay operationsDescription Status LED Test LED Fault LED Alarm relay(Green) (Yellow) (Re

Strona 20 - °CHeating °C

279.4 - Refrigerant systemVerify air and water flow rates are at proper levels beforeservicing. To maintain sealed circuitry integrity, do not install

Strona 21

286. Compare the subcooling temperature with the normaltemperature listed in Table 9. If the measured liquid linetemperature does not agree with the r

Strona 22 - °C10°C20°C30°C

29Table 16 - TroubleshootingFault Heating Cooling Possible cause SolutionMain power problems X X Green status LED Off Check line voltage circuit break

Strona 23

31 - SAFETY CONSIDERATIONSInstallation and servicing of air-conditioning equipment can behazardous due to system pressure and electrical components.On

Strona 24

30Table 16 - Troubleshooting (cont’d)Fault Heating Cooling Possible cause SolutionOnly compressor runs X X Thermostat wiring Check G wiring at heat pu

Strona 25

31Heating cycle analysisCooling cycle analysisHeat of extraction (absorption) or heat of rejection =________ Flow rate (l/s) x ________ Temp. differen

Strona 26

11 - START-UP CHECKLIST - 50RHE R-407C UNITCustomer: ___________________________________ Job name: __________________________________________________M

Strona 27

410. Provide ready access to water valves and fittings, and screw-driver access to unit side panels, discharge collar, and allelectrical connections.1

Strona 28 - Resistance (kOhm)

5Fig. 1 - Dimensions50RHE 006-012 015-024 030 036 042-048 060Overall cabinet mmA (width) 568 568 568 568 568 645B (depth) 1095 1095 1351 1351 1580 180

Strona 29 - Table 16 - Troubleshooting

6Fig. 2 - Typical installation - 50RHE unitsField-supplied transition tominimise pressure lossSupply airInsulated supply duct with atleast one 90° elb

Strona 30

73.3 - Unit locationThe following guidelines should be considered when choosinga location for a water-source heat pump unit:• Units are for indoor use

Strona 31

83.4 - Mounting the unitHorizontal units should be mounted using the factory-installedhangers. Proper attachment of hanging rods to building structure

Strona 32 - Printed in the Netherlands

93.7 - Piping connectionsDepending on the application, there are three types of water-source heat pump piping systems to choose from: water loop,groun