36
Table 4 — ICVC Display Data (cont)
EXAMPLE 17 — NET_OPT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
6. Press
NOTE: No variables are available for CCN read or write operation.
EXAMPLE 18 — VFD_CONF DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Enter password (4444 Factory Default).
6. Scroll down to highlight .
7. Press .
NOTE: Those parameters marked with a * shall not be downloaded to the VFD, but shall be used in other calculations and algorithms in the ICVC.
DESCRIPTION STATUS UNITS POINT DEFAULT
Loadshed Function
Group Number 0-16 ldsgrp 0
Demand Limit Decrease 0-60 % ldsdlta 20
Maximum Loadshed Time 0-480MIN maxshed60
CCN Occupancy Config:
Schedule Number 3-99 occ_num 3
Broadcast Option 0-1 DSABLE/ENABLE occbrcst DSABLE
Alarm Configuration
Re-Alarm Time 0-1440 MIN retime 30
Alarm Routing xxxxxxxx routing 10000000
DESCRIPTION STATUS UNITS POINT DEFAULT
Motor Nameplate Voltage 346-480 VOLTS motor_nv 460
Compressor 100% Speed 45.0-62.0 Hz comp_100 60.0
Line Freq=60 Hz? (No=50) 0/1 NO/YES line_frq YES
* Rated Line Voltage 346-600 VOLTS vfd_volt 460
* Rated Line Amps 10-1500 AMPS vfd_amps 200
* Rated Line Kilowatts 0-7200 kW vfd_rlkw 100
* Motor Rated Load KW 0-7200 kW mot_rlkw 100
* Motor Rated Load Amps 10-1500 AMPS mot_rla 200
Motor Nameplate Amps 10-1500 AMPS motorni 100
Motor Nameplate RPM 1500-3600 motorpm 3456
Motor Nameplate KW 0-5600 kW motorkw 100
Inverter PWM Frequency (0=4 k Hz, 1=2 k Hz) 0/1 pwm_freq 0
Skip Frequency 1 0.0-102.0 Hz skipfrq1 102.0
Skip Frequency 2 0.0-102.0 Hz skipfrq2 102.0
Skip Frequency 3 0.0-102.0 Hz skipfrq3 102.0
Skip Frequency Band 0.0-102.0 Hz skipband 0.0
Line Voltage % Imbalance 1-10 % v_unbal 10
Line Volt Imbalance Time 1-10 SEC v_time 10
Line Current % Imbalance 5-40 % lineim_i 40
Line Current Imbal Time 1-10 SEC lineim_t 10
Motor Current % Imbalance 5-40 % motim_i 40
Motor Current Imbal Time 1-10 SEC motim_t 10
Increase Ramp Time 5-60 SEC ramp_inc 30
Decrease Ramp Time 5-60 SEC ramp_dec 30
Single Cycle Dropout 0/1 DSABLE/ENABLE cycdrop DSABLE