
ELECTRICAL
OPTIONS PANEL
CONTROLBOX
AND COMPRESSOR
ACCESS DOOR
\
\
\
\
\
\
\,
INDOOR MOTOR
ACCESS DOOR
/
f
OUTDOOR AIR
SCREEN
(HIDDEN)
\\
\
\
CONDENSER COIL
ACCESS PANEL
ECONOMIZER
HOOD
/
BAROMETRIC
RELIEF DAMPER
HOOD
/
BASEPAN CONNECTIONS
ACCESS PANEL
FILTER ACCESS DOOR
Fig. 4 -- Panel and Filter Locations
ELECTRIC HEAT
ACCESS DOOR
Step 6 -- Install External Trap for Condensate
Drain -- The unit's 3/4-in. condensate dr_dn connections me
located on the bottom and side of the unit. Unit discharge
connections do not determine the use of &'ain connections;
either drain connection can be used with vertical or horizont;fl
applications. See Fig. 3 for locations.
When using the standard side &'ain connection, make sure
the plug (red) in the alternate bottom connection is tight before
installing the unit. See Fig. 5.
To use the bottom drfdn connection for a roof curb installa-
tion, relocate the factou-installed plug (red) from the bottom
connection to the side connection. A l/2-in, socket extension
can be used to remove the plug. See Fig. 5. The piping for the
condensate drain and external trap can be completed after the
unit is in place.
All units must have an external trap for condensate drain-
age. Install a trap at least 4-in. deep and protect against fieeze-
up. If drain line is installed downstream from the external trap,
pitch the line away from the unit fit 1-in. per 10 ft of run. Do not
use a pipe size smaller than the unit connection (3/4-in.). See
Fig. 6 and 7.
The 50PG units are provided with a removable condensate
pan for ease of cleaning. It is recommended that a union be
placed between the unit find condensate drainage to ease the
removal of the pan during servicing. Adequate clem'ance
should be allowed if removal of condensate pan is requiled.
Allow 54 in. between condensate pan access panel and any ob-
struction for complete lemoval.
Komentarze do niniejszej Instrukcji