MODULATING GAS HEATING CAPACITIES — 48N UNITS
(Natural Gas on All Units)
NOTES:
1. Ratings are approved for altitudes to 2000 ft. At altitudes over
2000 ft, ratings are 4% less for each 1000 ft above sea level.
2. At altitudes up to 2000 ft, the following formula may be used to calcu-
late air temperature rise:
3. At altitudes above 2000 ft, the following formula may be used:
4. Minimum allowable temperature of mixed air entering the heat
exchanger during half-rate (first stage) operation is 35 F. There is no
minimum mixture temperature limitation during full-rate operation.
5. Temperature rise limits: see table.
6. On VAV (variable air volume) applications set the zone terminals to
provide minimum unit heating airflow as indicated in the table upon
command from Heat Interlock Relay (HIR) function.
ELECTRIC HEATER CAPACITIES (460 V ONLY)
NOTES:
1. Minimum CFM is based on 200 per ton.
2. Maximum CFM is based on of 500 per ton for small chassis and 400 per ton for large chassis.
UNIT SIZE
(NOMINAL CAPACITY, TONS)
NOMINAL
CAPACITY
GAS INPUT
(1000 Btuh)
EFFICIENCY
(%)
OUTPUT CAPACITY
(1000 Btuh)
TEMP
RISE (F)
AIRFLOW (Cfm)
Stage 1 Stage 2 Minimum Maximum Min Max
N
(75)
75 Low Heat 108 800 81 87.5 648 10-40 5,250 37,500
75 High Heat 108 1200 81 87.5 972 20-50 5,250 37,500
P
(90)
90 Low Heat 108 800 81 87.5 648 10-40 6,300 45,000
90 Medium Heat 108 1200 81 87.5 972 20-50 6,300 45,000
90 High Heat 108 1600 81 87.5 1296 25-65 6,300 45,000
Q
(105)
105 Low Heat 108 800 81 87.5 648 10-40 7,350 52,500
105 Medium Heat 108 1200 81 87.5 972 20-50 7,350 52,500
105 High Heat 108 1600 81 87.5 1296 25-65 7,350 52,500
R
(120)
120 Low Heat 108 1200 81 87.5 972 15-45 8,400 60,000
120 Medium Heat 108 1600 81 87.5 1296 20-50 8,400 60,000
120 High Heat 108 2000 81 87.5 1620 25-55 8,400 60,000
S
(130)
130 Low Heat 108 1200 81 87.5 972 15-45 9,100 60,000
130 Medium Heat 108 1600 81 87.5 1296 20-50 9,100 60,000
130 High Heat 108 2000 81 87.5 1620 25-55 9,100 60,000
T
(150)
150 Low Heat 108 1200 81 87.5 972 15-45 9,100 60,000
150 Medium Heat 108 1600 81 87.5 1296 20-50 10,500 60,000
150 High Heat 108 2000 81 87.5 1620 25-55 10,500 60,000
't =
maximum output capacity
1.10 x air quantity
't =
maximum output capacity
(.24 x specific weight of air x 60) (air quantity)
UNIT SIZE
(NOMINAL CAPACITY, TONS)
NO. STAGES
LOW
(kW)
CAPACITY
PER
STAGE (%)
MED
(kW)
CAPACITY
PER
STAGE (%)
HIGH
(kW)
CAPACITY
PER
STAGE (%)
MIN
CFM
MAX
CFM
N (75) 2 108 50,100 144 50,100 190 50,100 15,000 37,500
P (90) 2 108 50,100 144 50,100 265 50,100 18,000 45,000
Q (105) 2 108 50,100 144 50,100 265 50,100 18,000 52,500
R (120) 2 144 50,100 265 50,100 300 50,100 24,000 60,000
S (130) 2 144 50,100 265 50,100 300 50,100 24,000 60,000
T (150) 2 144 50,100 265 50,100 300 50,100 24,000 60,000
Ratings and capacities (cont)