Carrier’s 48/50N Series commercial
packaged rooftops offer:
Puron
®
refrigerant (R-410A)
multiple efficiency and capacity
choices
electronic expansion valves
double wall foam panel construction
mixed air and final filter options
flexible blank section and plenum
options
non-overloading airfoil supply fan
ComfortLink DDC controller with
Navigator™ user interface
communication capability with i-Vu
®
,
BACnet*, Modbus†, or LonWorks**
BAS
•Novation
®
heat exchanger technology
with microchannel coil
scroll compressors with digital
compressor option
full capacity operation at 125 F
constant volume (CV)
staged air volume (SAV™)
variable air volume (VAV)
Humidi-MiZer
®
adaptive
dehumidification option
vertical or horizontal supply/return
configurations
mixed vertical and horizontal supply/
return configurations
optional return fan or modulating
power exhaust
gas heat with optional modulating
control
electric heat with optional SCR control
hydronic heat option
Features/Benefits
Carrier's 48/50N commercial
packaged unit offers performance,
innovation and reliability. Key
components of the package
provide design flexibility, quality,
interoperability and ComfortLink
controls.
WEATHEREXPERT
48/50N2,N3,N4,N5,N6,N7,N8,N9
Packaged Rooftop Cooling Units
with Gas Heat, Optional Electric Heat,
or Hydronic Heat
and ComfortLink Controls
75 to 150 Nominal Tons
Product
Data
a48-8672
We a t h
erExp
ert
Przeglądanie stron 0
1 2 3 4 5 6 ... 91 92

Podsumowanie treści

Strona 1 - We a t h

© Carrier Corporation 2013 Form 48/50N-1PDCarrier’s 48/50N Series commercial packaged rooftops offer:• Puron® refrigerant (R-410A)• multiple efficienc

Strona 2 - Table of contents

10UNIT DESIGN AIRFLOW LIMITSNOTE: Applies for standard filters only; additional filtration options mayreduce maximum allowed airflow.UNIT SIZE(NOMINAL

Strona 3

11TWO-STAGE GAS HEATING CAPACITIES - 48N UNITS (Natural Gas on All Units)NOTES:1. Ratings are approved for altitudes to 2000 ft. At altitudes over2000

Strona 4

12MODULATING GAS HEATING CAPACITIES — 48N UNITS(Natural Gas on All Units)NOTES: 1. Ratings are approved for altitudes to 2000 ft. At altitudes over200

Strona 5 - Gas heat units (48N units)

1348/50N SIZES N-T (75-150 TONS NOMINAL CAPACITY) LEGEND *Base unit includes: economizer dampers and hoods, filter tracks less filter

Strona 6

1448/50N SIZES N-T (75-150 TONS NOMINAL CAPACITY) (cont) BASE UNIT N P Q R S TNOMINAL CAPACITY (tons) 75 90 105 120 130 150HUMIDI-MIZER® COI

Strona 7

1548/50N SIZES N-T (75-150 TONS NOMINAL CAPACITY) (cont)BASE UNIT N P Q R S TNOMINAL CAPACITY (tons) 75 90 105 120 130 150OPTIONAL POWER EXHAUST Pow

Strona 8 - Model number nomenclature

16ABCDEFMULTIPLE UNIT MINIMUM SEPARATIONa48-8682MINIMUM SPACING (ft)UNITABCDEF48 Series12 8 1210101050 Series10 8 8 10 10 10Physical data (cont)

Strona 9 - Quality Assurance

17REFRIGERANT CHARGEUNIT SIZE(NOMINAL CAPACITY, TONS)UNIT CONFIGURATIONCHARGE (LB) CHARGE (LB)UNITS WITHOUT HUMIDI-MIZER® SYSTEMUNITS WITH HUMIDI-MIZE

Strona 10 - Ratings and capacities

18FAN AND DRIVE INFORMATIONFANMOTOR HPMOTOR RPMMOTOR SHAFT SIZE (in.)FAN RPMFAN SHAFT SIZE (in.)DRIVE SHEAVE BROWNINGBUSHING TYPEDRIVEN SHEAVE BROWNIN

Strona 11 - (Natural Gas on All Units)

19FAN AND DRIVE INFORMATION (cont)MOTORSFANMOTOR HPMOTOR RPMMOTOR SHAFT SIZE (in.)FAN RPMFAN SHAFT SIZE (in.)DRIVE SHEAVE BROWNINGBUSHING TYPEDRIVEN S

Strona 12 - Ratings and capacities (cont)

2Design flexibilityThe 48/50N Series rooftop units with ComfortLink controls are designed to meet all customer requirements for new construction, repl

Strona 13 - Physical data

20STAGING SEQUENCES SIZE N STAGING SEQUENCE WITH MLV (75 TON NOMINAL CAPACITY)*Minimum load valve (MLV). MLV is enabled on Circuit A when decreas-ing

Strona 14 - Physical data (cont)

21STAGING SEQUENCES (cont)SIZE P, Q STAGING SEQUENCE WITH DIGITAL COMPRESSOR (90 AND 105 TON NOMINAL CAPACITY)SIZE R, S, T STAGING SEQUENCE (120-150 T

Strona 15

22 OPERATING WEIGHTS OF OPTIONS AND ACCESSORIES (lb)OPTION OR ACCESSORY48/50N UNIT SIZE (TON NOMINAL CAPACITY)N(75)P(90)Q(105)R(120)S(130)T(150)Econom

Strona 16

23 OPERATING WEIGHTS OF OPTIONS AND ACCESSORIES (lb) (cont)NOTE: Please refer to E-CAT for selection.OPTION OR ACCESSORY48/50N UNIT SIZE (TON NOMINAL

Strona 17 - REFRIGERANT CHARGE

24ITEM OPTION* ACCESSORY† SPECIAL ORDER**GAS HEAT (48N units only) Low, Medium or High Gas Heat — Aluminized Heat Exchanger X Low, Medium or High

Strona 18

25LEGEND*Factory installed.†Field installed.**A special order is offered to meet specific customer requirements. Quotationsfor special order options c

Strona 19

26Chassis arrangements (48 Series units)Standard chassis — The standard chassis may be pro-vided with a bottom or side return air opening. The returna

Strona 20

27with optional modulating power exhaust or return fan inconjunction with an optional economizer. Factory-installedoptional electric heat is available

Strona 21 - STAGING SEQUENCES (cont)

2848N UNIT SIZES N, P, Q (75-105 TON NOMINAL CAPACITY)A48-8684Base unit dimensions

Strona 22

2948N UNIT SIZES N, P, Q (75-105 TON NOMINAL CAPACITY) NOMINAL CAPACITY/EFFICIENCYEXTENDED CHASSISSUPPLY FANFIELD USE FILTER SECTIONBLANK

Strona 23

3Novation® heat exchanger technologyThe Novation heat exchanger design with microchannel condenser coil is a robust, cost effective alternative to tra

Strona 24 - Options and accessories

3048N UNIT SIZES R, S, T (120-150 TON NOMINAL CAPACITY)A48-8685Base unit dimensions (cont)

Strona 25

3148N UNIT SIZES R, S, T (120-150 TON NOMINAL CAPACITY) *Vertical discharge only.NOMINAL CAPACITY/EFFICIENCYEXTENDED CHASSISHIGH GAS HEAT*

Strona 26 - BLANK SECTION

3250N UNITS SIZES N, P, Q (75-105 TON NOMINAL CAPACITY) A50-8823Base unit dimensions (cont)

Strona 27

3350N UNIT SIZES N, P, Q (75-105 TON NOMINAL CAPACITY) NOMINAL CAPACITY/EFFICIENCYEXTENDED CHASSISSUPPLY FANFIELD USE FILTER SECTIONBLANK

Strona 28 - Base unit dimensions

3450N UNITS SIZES R, S, T (120-150 TON NOMINAL CAPACITY)a50-8824Base unit dimensions (cont)

Strona 29

3550N UNIT SIZES R, S, T (120-150 TON NOMINAL CAPACITY) NOMINAL CAPACITY/EFFICIENCYEXTENDED CHASSISFIELD USE FILTER SECTIONBLANK SECTION2-

Strona 30 - Base unit dimensions (cont)

36 0'-1"[25.4] 0'-3"[76.2] 0'-1 3/4"[44]"D" SUPPORTSEE CONDENSERSECTION 10'-8 7/8"[3274] "C&quo

Strona 31 - *Vertical discharge only

3748N ROOF CURB SIZES N, P, Q (75-105 TON NOMINAL CAPACITY) *Use Applied Rooftop Builder program to select the proper roof curb.NOTE: Dimensions are

Strona 32

38 0'-1"[25.4] 0'-3"[76.2] 0'-1 3/4"[44]"D" SUPPORTSEE CONDENSERSECTION 10'-8 7/8"[3274] "C&quo

Strona 33

3950N ROOF CURB SIZES N, P, Q (75-105 TON NOMINAL CAPACITY) *Use Applied Rooftop Builder program to select the proper roof curb.NOTE: Dimensions are i

Strona 34

4Fan modulationThe ComfortLink controller maintains supply duct pressure on VAV models by monitoring the factory-installed duct pressure transducer an

Strona 35

40ROOF CURB CONDENSER SECTIONa48-8745ROOF CURB CONDENSER SUPPORT UNIT SIZE NOMINAL TONSCOND COILS 2V COND COIL 3VDIM.DDIM.E75 ALL YES — 129.50 —90 ST

Strona 36 - Accessory dimensions

41COMPONENT PRESSURE DROPS (in. wg)SIZES N, P, Q (75-105 TON NOMINAL CAPACITY) LEGENDCOMPONENTAIRFLOW (cfm)15,000 19,000

Strona 37 - NOMINAL CAPACITY)

42COMPONENT PRESSURE DROPS (in. wg)SIZES R, S, T (120-150 TON NOMINAL CAPACITY) LEGENDCOMPONENTAIRFLOW (cfm)24,000 28,000 32,000 36,000 40,000 44,

Strona 38 - Accessory dimensions (cont)

43Please refer to the Applied RTUBuilder software for theunit electrical data. The unit electrical data may also befound in the unit Installation Inst

Strona 39

44Control componentsThe 48/50N Series rooftops use the ComfortLink controlsystem that has been developed for use in Carrier Com-mercial equipment. The

Strona 40

45controls and provides an additional stage of capacity aswell as low load coil freeze protection. The control also in-tegrates the use of an economiz

Strona 41 - Performance data

46heat capacity based on set point and supply-air tempera-ture. The valve control logic will modulate the heating ca-pacity to match the calculated de

Strona 42 - Performance data (cont)

47displayed by the ComfortLink scrolling marquee in partsper million (ppm).Outdoor air cfm control — Minimum space ventilationrequirements can also be

Strona 43 - Electrical data

484 to 20 mA signal. It can be connected to terminals 8and 9 on TB202.• Remote Static Pressure Reset Set Point — A remotesupply air temperature set po

Strona 44 - Controls

49• For units connected to the CCN network the user canalso display all the unit information including I/O valuesMaintenance, Configuration, Service,

Strona 45 - Heating control options

5• VAV units provide multiple stage,cooling capacity control forimproved part load operation andgreater efficiency• optional digital compressors provi

Strona 46 - Controls (cont)

50Constant volume and staged air volume space tem-perature sensor control — If the space temperature op-eration has been selected using a T55, T56, or

Strona 47 - Control interface

51mode the control will energize the heat interlock relaywhich will signal the terminals to open to the heating posi-tion. Note that for the linkage s

Strona 48

52motor, integrated gas control (IGC) board, 2-stage gasvalve, manifold, and safeties. The modulating system incor-porates an additional modulating ga

Strona 49 - Sequence of operation

53Ductwork — Secure vertical discharge ductwork to theroof curb. Interior installation may proceed before the unitis set in place on the roof. For hor

Strona 50

54B"J"AUXILIARY COIL LOCATIONLOCATION OF COIL TRACKSAUXILIARY COIL LOCATION — in.UNITSIZES 48/50N (TONS)HEIGHT B DISTANCE JN, P, Q (75-105)

Strona 51 - 48 Series gas heat units

55MAIN POWER SUPPLY ENTRYNATURAL GASSUPPLY LINEWITH SHUTOFFCONTROLWIRINGENTRYCONDENSATEDRAIN CONNECTIONSTANDARD UNITSa48-8675Typical piping and wiring

Strona 52

56460VONLYPOWER SCHEMATIC — SIZE N SHOWN (75 TON NOMINAL CAPACITY)a48-8658Typical wiring schematics

Strona 53 - Application data

57460VONLYa48-8659POWER SCHEMATIC — SIZES P, Q, R, S, T SHOWN (90-150 TON NOMINAL CAPACITY)

Strona 54 - Application data (cont)

58CONTROL SECTION — 48/50N UNITSa48-8660Typical wiring schematics (cont)

Strona 55 - Typical piping and wiring

59CONTROL SECTION — 48/50N UNITS (cont)a48-8661

Strona 56 - Typical wiring schematics

6Electric heat units (50N units)The 50N units may be equipped with factory-installed electric heat, with 3 heat sizes available for every unit. The he

Strona 57

60CONTROL SECTION — 48/50N UNITS (cont)a48-8662Typical wiring schematics (cont)

Strona 58

61MODULATING GAS HEAT SCHEMATICa48-8663

Strona 59

62STANDARD GAS HEAT SCHEMATICa48-8664Typical wiring schematics (cont)

Strona 60

63ELECTRIC HEAT SCHEMATICA50-8782

Strona 61 - MODULATING GAS HEAT SCHEMATIC

64460-V, 24-V CONTROL SCHEMATICA48-8665Typical wiring schematics (cont)

Strona 62 - STANDARD GAS HEAT SCHEMATIC

65575-V, 24-V CONTROL SCHEMATICA48-8666

Strona 63 - A50-8782

66STANDARD GAS HEAT, 2 MODULE SCHEMATICA48-8667Typical wiring schematics (cont)

Strona 64 - A48-8665

67STANDARD GAS HEAT, 3 MODULE SCHEMATICA48-8668

Strona 65 - A48-8666

68STANDARD GAS HEAT, 4 MODULE SCHEMATICA48-8669Typical wiring schematics (cont)

Strona 66 - A48-8667

69STANDARD GAS HEAT, 5 MODULE SCHEMATICA48-8670

Strona 67 - A48-8668

7Condenser Section• Novation® MCHX technology• High-efficiency option• Replaceable core filter drier option• R-410A refrigerantHeating Systems• Gas,

Strona 68 - A48-8669

70LEGEND FOR TYPICAL CONTROL WIRING SCHEMATICSACCSY — AccessoryACC’Y — AccessoryAF — Air FoilAN — AnalogAO — Anaolog OutputBR — Blower RelayC—Compress

Strona 69 - A48-8670

71Packaged Rooftop Cooling Unit with Gas Heat and ComfortLink ControlsHVAC Guide Specifications —Section 48N2,N3,N4,N5,N6,N7,N8,N9Size Range: 75 to 15

Strona 70

72contain a factory-installed nonferrous main con-densate drain connection.9. Top cover of airside section to be sloped to pre-vent standing water.10.

Strona 71 - Heat and ComfortLink Controls

7310. On-board storage of unit manufacturer's cus-tomer user settings, retrievable from thekeypad.11. RS485 communications capability (accessoryc

Strona 72

74shall be provided when unit is equippedwith modulating gas heat option.6) Adaptive optimal start shall determinethe time unit will commence cooling

Strona 73

7521) Space Temperature Offset function shallpermit occupants to adjust space tem-perature set point by ±5° F using T-56space sensor (equipped with sl

Strona 74

76N. Electrical Requirements:All unit power wiring shall enter unit cabinet at a sin-gle location.O. Special Features:1. Digital Compressor:A digital

Strona 75

77respectively (ASTM D2247-92 and ASTMD870-92). Corrosion durability shall be con-firmed through testing to be no less than1000 hours salt spray per A

Strona 76

7817. Belt Guard:Unit shall be equipped with belt guard on allbelt-driven fans. The guard shall completelyenclose the drive system and be removable fo

Strona 77

79heating supply air temperature set point.Turndown ratio to be at least 7:1 for thesmallest low heat option, ranging up to18:1 for the high heat opti

Strona 78

848N2 DN6 0 Option CodeFactory Options48 – Cooling Unit with Gas Heat See note belowConfigurationN2 – Vertical Suppy/Return, CV/SAV ComfortLink Contro

Strona 79

80k. All factory wiring penetrating through thepanel is protected in 'RIGID' type metalconduit.32. Non-Fused Disconnect:A non-fused electric

Strona 80

81protect the unit if an abnormal condition isdetected.45. BACnet Communication Option:Shall provide factory-installed communicationcapability with a

Strona 81

82Packaged Rooftop Cooling Unit with ComfortLink Controls and Optional Electric or Hydronic HeatHVAC Guide Specifications —Section 50N2,N3,N4,N5,N6,N7

Strona 82 - HVAC Guide Specifications —

832. Factory rubber-in-shear mounted for vibrationisolation.3. Reverse rotation protection capability.4. Crankcase heaters shall only be activated dur

Strona 83

84G. Outdoor-Air Hood Assembly:Factory-installed motorized outdoor-air damper shallallow intake of up to 100% nominal airflow (on unitsnot equipped wi

Strona 84

857) Adaptive optimal stop shall turn off thecompressors a preset amount of timebefore the end of the occupied mode toconserve energy (CV only).8) Ale

Strona 85

8622) Lead-lag function shall distribute startsbetween the two refrigeration circuits inan effort to equalize the running time onthe two circuits.23)

Strona 86

87P. Electrical Requirements:All unit power wiring shall enter unit cabinet at a sin-gle location.Q. Special Features:1. Digital Compressor:A digital

Strona 87

88respectively (ASTM D2247-92 and ASTMD870-92). Corrosion durability shall be con-firmed through testing to be no less than1000 hours salt spray per A

Strona 88

8917. Belt Guard:Unit shall be equipped with belt guard on allbelt driven fans. The guard shall completelyenclose the drive system and be removable fo

Strona 89

950N2 DN6 0 Option CodeFactory Options50 – Cooling Only UnitSee note belowConfigurationN2 – Vertical Suppy/Return, CV/SAV ComfortLink ControlsDesign R

Strona 90

902) Full output heating on heating controlcommand.3) Tempering heat control, based on user-configured ventilation supply air temper-ature set point,

Strona 91

9132. Non-Fused Disconnect:A non-fused electrical disconnect for main unitpower shall be factory installed. The disconnectshall be an interlocking thr

Strona 92

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Pg 9