UNIT DESIGN AIRFLOW LIMITS
NOTE: Applies for standard filters only; additional filtration options may
reduce maximum allowed airflow.
UNIT SIZE
(NOMINAL CAPACITY, TONS)
UNIT TYPE MINIMUM COOLING CFM MAXIMUM CFM
N
(75)
48N Low Heat 15,000 37,500
48N High Heat 15,000 37,500
50N Electric Heat 15,000 37,500
50N No Heat 15,000 37,500
P
(90)
48N Low Heat 18,000 45,000
48N Medium Heat 18,000 45,000
48N High Heat 18,000 45,000
50N Electric Heat 18,000 45,000
50N No Heat 18,000 45,000
Q
(105)
48N Low Heat 21,000 47,000
48N Medium Heat 21,000 47,000
48N High Heat 21,000 47,000
50N Electric Heat 21,000 47,000
50N No Heat 21,000 47,000
R
(120)
48N Low Heat 24,000 60,000
48N Medium Heat 24,000 60,000
48N High Heat 24,000 60,000
50N Electric Heat 24,000 60,000
50N No Heat 24,000 60,000
S
(130)
48N Low Heat 26,000 60,000
48N Medium Heat 26,000 60,000
48N High Heat 26,000 60,000
50N Electric Heat 26,000 60,000
50N No Heat 26,000 60,000
T
(150)
48N Low Heat 30,000 60,000
48N Medium Heat 30,000 60,000
48N High Heat 30,000 60,000
50N Electric Heat 30,000 60,000
50N No Heat 30,000 60,000
Ratings and capacities