Carrier 17/19EX Dokumentacja Strona 268

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 267
Red LED
If the LED is blinking continuously at a 2-second rate, it is indicating proper operation. If it is
lit continuously it indicates a problem requiring replacement of the module. Off continuously
indicates that the power should be checked. If the red LED blinks 3 times per second, a
software error has been discovered and the module must be replaced. If there is no input
power, check fuses and the circuit breaker. If fuse is good, check for shorted secondary of
transformer, or if power is present to the module, replace the module.
Green LEDs
There are 1 or 2 green LEDs on each type of module. These LEDs indicate communication
status between different parts of the controller and the network modules as follows:
LID Module
Upper LED
— Communication with CCN network, if present; blinks when communication
occurs.
Lower LED
Communication with PSIO module; must blink every 5 to 8 seconds when the
LID default screen is displayed.
Przeglądanie stron 267
1 2 ... 263 264 265 266 267 268 269 270 271 272 273 ... 436 437

Komentarze do niniejszej Instrukcji

Brak uwag