Carrier 17/19EX Dokumentacja Strona 192

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 191
b. Valve positions: Close valves 3 and 4, open valves 2 and 5.
c. Turn on pumpout condenser water.
d. Run the pumpout compressor until the suction reaches 15 in. Hg (50 kPa abs). Monitor
pressures on the LID and on refrigerant gages.
e. Close valve 6.
f. Turn off pumpout compressor.
g. Close valves 1, 2, and 5 (all valves are now closed).
h. Turn off pumpout condenser water.
i. Continue pumpdown function on the LID to turn off machine water pumps and lock out
the machine compressor from operation.
Valve
1 2 3 4 5 6 7 8 9 10 11
Condition
CC CCCCC
Przeglądanie stron 191
1 2 ... 187 188 189 190 191 192 193 194 195 196 197 ... 436 437

Komentarze do niniejszej Instrukcji

Brak uwag