Product
Data
50JZ
Single-Package
Heat Pump
Units
with Puron® (R-410A) Refrigerant
2 to 5 Nominal Tons
Copyright 2000 Carrier Corporation Form 50JZ-1PD
Single-Package Products with
Energy-Saving Features and Puron®
refrigerant.
• 12 SEER
• HSPF up to 7.2
• Low Sound Levels
Features/Benefits
One-piece Heat Pump unit with
optional electric heater, low
installation cost, dependable
performance and easy maintenance.
Efficient operation
High-efficiency design
with SEERs
(Seasonal Energy Efficiency Ratio)
of 12.0.
Puron® Environmentally Sound
Refrigerant
is Carrier’s unique
refrigerant designed to help protect the
environment. Puron is an HFC
refrigerant which does not contain
chlorine that can harm the ozone layer.
The most important advantage of
Puron refrigerant is that it has not been
banned in future air conditioning
systems as the traditional refrigerant
R-22 has been. Puron refrigerant is in
service in over 100,000 systems
proving highly reliable,
environmentally sound performance.
Easy Installation
Factory-assembled package
is a
compact, fully self-contained, heat
pump unit that is pre-wired, pre-piped,
and pre-charged for minimum
installation expense. 50JZ units are
available in a variety of standard
capacity ranges with voltage options to
meet residential and light commercial
requirements. Units install easily on a
rooftop or at ground-level.
Durable, dependable
components
Compressors
are designed for high
efficiency. Each compressor is
hermetically sealed against
contamination to help promote longer
life and dependable operation.
UNIT 50JZ
Przeglądanie stron 0
1 2 3 4 5 6 ... 27 28

Podsumowanie treści

Strona 1 - Features/Benefits

ProductData 50JZSingle-PackageHeat PumpUnits with Puron® (R-410A) Refrigerant 2 to 5 Nominal Tons Copyright 2000 Carrier Corporation Form 50JZ-1PD Si

Strona 2 - Table of contents

10I Determine cooling and heating requirements at design conditions:Given:Required Cooling Capacity (TC) . . . . . . . . . 33,500 BtuhSensible Heat

Strona 3 - ARI* capacities

11Performance dataCOOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60*At 75°F entering

Strona 4 - Physical data

12Performance data (cont)COOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60*At 75°F e

Strona 5 - Options and accessories

13Performance data (cont)COOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60*At 75°F e

Strona 6 - ECONOMIZER

14Performance data (cont)COOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60*At 75°F e

Strona 7 - 50JZ 024-036 Dimensions

15Performance data (cont)COOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60*At 75°F e

Strona 8 - 44.5 [1.75]

16Performance data (cont)COOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60*At 75°F e

Strona 9 - Accessory dimensions

17LEGENDEwb – Entering Wet-BulbkW – Total Unit Power InputSHC – Sensible Heat Capacity (1000 Btuh)TC – Total Capacity (1000 Btuh) (net)NOTES:1. Rating

Strona 10 - Selection Procedure

18WET COIL DELIVERY—HORIZONTAL AND DOWNFLOW DISCHARGE UNIT 50JZ 024-060*Air delivery values are based on operating voltage of 230 v or 460 v, wet coil

Strona 11 - Performance data

19INDOORTHERMOSTATDISCONNECTPER NEC*FROMPOWERSOURCERETURNAIRTOP COVER*NEC - NATIONAL ELECTRICAL CODETypical piping and wiringROOFRETURN-AIRFLEXIBLE DU

Strona 12 - Performance data (cont)

2 Vibration isolation provides quiet operation. Compressors have internal high-pressure and overcurrent protection. Convertible duct configuration U

Strona 13

20Condensate trap — A 2-in. condensate trap must be fieldsupplied.Ductwork — Secure downflow discharge ductwork to roofcurb. For horizontal discharge ap

Strona 14

21Electrical dataUNITSIZE50JZV-PH-HzVOLTAGERANGECOMPRESSOROUTDOORFAN MOTORINDOORFAN MOTOR ELECTRIC HEAT POWER SUPPLY†Min Max RLA LRA FLA FLA Nominal k

Strona 15

22452=5v457=7v455=2vLEGENDFLA — Full Load AmpsHACR — Heating, Air Conditioning and RefrigerationIFM — Indoor-Fan MotorLRA — Locked Rotor AmpsMCA — Min

Strona 16

23Typical wiring schematic — 208/230-1-60 shown

Strona 17

24Typical wiring schematic — 208/230-3-60 shown

Strona 18 - FILTER PRESSURE DROP (In. wg)

25Typical wiring schematic — 460-3-60 shown

Strona 19 - Typical piping and wiring

26Sequence of operationWhen power is supplied to unit, the transformer (TRAN) isenergized.On units with crankcase heater, heater is also energized.Coo

Strona 20 - Application data

27Packaged Heat Pump Units Constant Volume ApplicationHVAC Guide SpecificationsSize Range: 2 to 5 Tons, Nominal CoolingCarrier Model Number: 50JZPart

Strona 21 - Electrical data

Carrier Corporation • Indianapolis, IN 46231 7/00Manufacturer reserves the right to discontinue, or change at any time, specifications or designs wit

Strona 22

3 Model number nomenclatureARI* capacities COOLING CAPACITIES AND EFFICIENCIES 50JZ 024Model No. 50JZ – Single Package... . Heat Pump Nominal C

Strona 23

4 Physical data * Required filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling airflow

Strona 24

5 Factory-installed optionsCoil options include copper/copper and vinyl-coated construction for refrigerant coils. Units are shipped standard with c

Strona 25

6 ECONOMIZERFILTER RACK MANUAL OUTSIDE AIR DAMPERDAMPERBLADEMANUAL OUTSIDEAIR HOODREPLACEMENTPANEL7

Strona 26 - Controls

7 Base unit dimensions—50JZ024-036REQ’D CLEARANCES FOR OPERATION AND SERVICING. IN.(MM)EVAPORATOR COIL ACCESS SIDE ... 36(914)POWER ENTRY S

Strona 27 - Guide specifications

8Base unit dimensions—50JZ042-060REQUIRED CLEARANCE FOR OPERATION AND SERVICINGin. [mm]EVAP. COIL ACCESS SIDE....

Strona 28 - Guide specifications (cont)

9Accessory dimensionsUNIT SIZEODS CATALOG ORDERING NO. Ain. [mm]Bin. [mm]Cin. [mm]Din. [mm]FLAT CURB50JZ024-036CPRFCURB006A00 8 [203] 11-27/32 [301] 3