Installation Instructions40MAQHigh Wa ll Ductless Split Sys temSizes 09 to 36NOTE: Read the entire instruction manual before starting theinstallation.
10TROUBLESHOOTINGFor ease of service, the systems are equipped with diagnostic codedisplay LEDs on both the indoor and outdoor units. The indoordiagno
2SAFETY CONSIDERATIONSInstalling, starting up, and servicing air-- conditioning equipmentcan be hazardous due to system pressures, electrical componen
3PARTS LISTPart No. Name of Part Qty1 Indoor Unit 12 Mounting Plate 13 M o u n t i n g S c r e w A S T 3 . 9 x 2 5 --- C --- H 54 Anchor 55 Air Filter
4SYSTEM REQUIREMENTSAllow sufficient space for airflow and servicing unit. See Fig. 3 for minimum required distances between unit and walls or ceiling
5DIMENSIONS -- INDOORA150772Fig. 2 --- Indoor Unit DimensionsTa ble 3—Indoor Unit DimensionsHIGH WALL UNIT SIZE 9K 12K 9K 12K 18K 24K 30K 36KVoltage (
6INSTALLATION TIPSIdeal installation locations include:IndoorUnitS A location where there are no obstacles near inlet and outlet area.S A location whi
7ELECTRICAL DATATable 4—Electrical DataHIGH WALL UNITSIZEINDOOR FANMAX FUSE CB AMPV --- P h --- H z FLA HP9K1 1 5 --- 1 --- 6 00.33 0.053Refer to outd
8ObliqueDŽ90RoughnessBurrA150767Fig. 13 --- Pipe Cuttingc. Remove all the burrs from the cut cross section of the pipeavoiding any burrs inside the tub
9START-- UPTest OperationPerform a test operation after completing gas leak and electricalsafety check (see Fig. 19).Manual control buttonAUTO/COOLA14