Software Revs 3,5,6,8,10, 12 Infinity /Evolution Troubleshooting (Rev. 2)
10-12-2006
15
Checking Airflow, Static Pressure and RPM in the Service Menu
• The airflow displayed in the Service screen is requested airflow, not actual airflow.
• The static pressure displayed in the Service Screen is calculated based on requested
airflow, RPM and known system characteristics.
• The RPM displayed in the Service screen is actual RPM.
• Accuracy of static pressure readings is limited on some furnaces when RPM reaches
1100
RPM data can be used as an indicator of restrictive ductwork. When RPM maxes out, the Blower
Cutback flag is communicated to the furnace or fan coil control. This begins the Blower Cutback
algorithm which protects the motor from running at extreme conditions. The cutback algorithm is
explained in this document in the description of the EXCESS STATIC PRESSURE system
event.
Most furnaces and fan coils will deliver the requested airflow up to the maximum RPM. When a
system is not able to deliver the requested CFM at high static pressures, the accuracy of the
static pressure calculation is limited. See airflow information in Product Data to determine airflow
performance.