APPENDIX A CCN TABLES (cont)
CONFIGURATION SCREEN (TYPE 10)
OPTIONS2 (Options Configuration)
DISPLAY (STDU SETUP)
SCHEDOVR (TIMED OVERRIDE SETUP)
ALARMDEF (Alarm Definition Table)
*Unit size dependent.
DESCRIPTION STATUS DEFAULT UNITS POINT
Control Method 0 = Switch
1 = 7 day sched.
2 = Occupancy
3 = CCN
0CONTROL
Loading Sequence Select 1 = Equal loading
2 = Staged loading
1 SEQ_TYPE
Lead/Lag Circuit Select 1 = Automatic
2 = Circuit A leads
3 = Circuit B leads
*LEAD_TYP
Cooling Setpoint Select 0 = Single
1 = Dual, remote switch controlled
2 = Dual, 7-day occupancy
3 = Dual CCN occupancy
4 = 4-20 mA input
5 = External POT
0CLSP_TYP
Heating Setpoint Select 0 = Single
1 = Dual, remote switch controlled
2 = Dual, 7 day occupancy
3 = Dual CCN occupancy
4 = 4-20 mA input
0 HTSP_TYP
Ramp Load Select Enable/Disable Disable RAMP_EBL
Heat Cool Select Cool/Heat Cool HEATCOOL
High LCW Alert Limit 2 to 60 60.0 ^F LCW_LMT
Minutes off time 0 to 15 0 min DELAY
Deadband Multiplier 1.0 to 4.0 1.0 Z_GAIN
Ice Mode Enable Enable/Disable Disable ICE_CNFG
DESCRIPTION STATUS DEFAULT UNITS POINT
Service Password nnnn 1111 PASSWORD
Password Enable Enable/Disable Enable PASS_EBL
Metric Display Off/On Off DISPUNIT
Language Selection 0 = ENGLISH
1 = FRANCAIS
2 = ESPANOL
3 = PORTUGUES
0LANGUAGE
DESCRIPTION STATUS DEFAULT UNITS POINT
Schedule Number 0-99 0 SCHEDNUM
Override Time Limit 0-4 0 hours OTL
Timed Override Hours 0-4 0 hours OTL_EXT
Timed Override Yes/No No TIMEOVER
DESCRIPTION STATUS DEFAULT UNITS POINT
Alarm Routing Control 00000000 00000000 ALRM_CNT
Equipment Priority 0 to 7 4 EQP_TYPE
Comm Failure Retry Time 1 to 240 10 min RETRY_TM
Re-alarm Time 1 to 255 30 min RE-ALARM
Alarm System Name XXXXXXXX Chiller ALRM_NAM