Cooling Set Point (4 to 20 mA) —
A field supplied
and generated, externally powered 4 to 20 mA signal can be
used to provide the leaving fluid temperature set point. Connect
the signal to TB6-3,5 (+,–). See Table 29 for instructions to
enable the function. Figure 26 shows how the 4 to 20 mA sig-
nal is linearly calculated on an overall 10 F to 80 F range for
fluid types (Configuration mode, sub-mode OPT1, item
FLUD) 1 or 2. The set point will be limited by the fluid
(FLUD) type. Be sure that the chilled water loop is protected at
the lowest temperature.
0
1
234
5
6
7
8
9
10
TEMPERATURE DIFFERENCE (EWT-LWT) DEGREES F
TEMPERATURE DIFFERENCE (EWT-LWT) DEGREES C
0
.55
1.1
1.7
2.2
2.8
3.3
3.9
4.4
5.0
5.5
DESIGN RISE
RESET
AMOUNT
10
9
8
7
6
5
4
3
2
1
RESET AMOUNT DEGREES F
RESET AMOUNT DEGREES C
5.5
5.0
4.4
3.8
3.3
2.8
2.2
1.7
1.1
.55
0
CHANGE IN
LWT SET
POINT
FULL COOL
RESET T
∆
NO COOL
RESET T
∆
LEGEND
Fig. 25 — Return Water Reset
EWT —
Entering Water (Fluid) Temperature
LWT —
Leaving Water (Fluid) Temperature
100
(38)
80
(27)
60
(15)
40
(4.4)
20
(-7)
0
(-17)
4 6.3 8.6 10.9 13.1 15.4 17.7 20
4 TO 20 mA SIGNAL TO EMM
SET POINT, F (C)
90
(32)
70
(21)
50
(10)
30
(-1)
10
(-12)
(FLUD = 2) MINIMUM
SET POINT 14 F (-10 C)
(FLUD = 1) MINIMUM
SET POINT 38 F (3.3 C)
MAXIMUM
SET POINT
70 F (21.1 C)
Fig. 26 — Cooling Set Point (4 to 20 mA)
EMM —
Energy Management Module