ZONECC(2,4,8)KIT-BInstallation and Start-Up InstructionsTABLE OF CONTENTSPageSAFETY CONSIDERATIONS...1
Option 15—Enable AUTO modeOption 16—Enable Comfort Heat modeOption 18—Humidity offset adjustmentOption 19—Outdoor air temperature offset adjustmentOpt
on, it will remain on until the demand is satisfied. The followingcycle will start with the heat pump. Outdoor temperatures of 5, 10,15, 20, 25, 30, 3
shut down the equipment when the LAT temperature reaches itslimit. If the equipment is shut down by a LAT or HPT limit trip,the small ’equipment on’ t
Step 3—Quick Check of Equipment OperationEither this or the next step (Step 4) may be used for initial startup.This check runs equipment for only 2 mi
applications, this is an improvement over using an externalhumidistat, which only supplies humidity when auxiliary heatis on.2. Fan Humidify Mode—This
3. Cool to Dehumidify Mode—This mode tells the system tooperate the compressor, with limits, when there is a dehu-midify demand and there is no coolin
removed to enable the DEHUM input. See Table 6 and Fig. 31through 34. When a dehumidify demand exists, the furnace controlreduces the blower airflow b
4. Press HOLD/END key to exit.Select system Mode:1. Press MODE button to select HEAT or COOL.2. Press HOLD/END button to turn on HOLD icon.3. Press UP
SMART SENSOR OPERATIONNOTE: Refer to Smart Sensor Installation and Start-Up Instructions for proper installation and set-up procedure.The Smart Sensor
changing according to the program schedule. Cancelling theHOLD function changes the set points to whatever is in theprogram schedule for that period o
• User Interface — Each installation has only 1 User Interface.This is the command center for the entire system, and it willtypically be located in Zo
(1.) Auxiliary Heat Lockout (System is configured as aheat pump and configuration Option No. 8 is active).(2.) Dual Fuel Setup (DIP switch No. 8 OFF.
Table 6—Wiring Diagram Reference ChartEQUIPMENTSELECTION1-SPEEDAC2-SPEEDAC1-SPEEDHP2-SPEEDHP1-StageFurnaceFig. 15 Fig. 16 Fig. 17 Fig. 182-StageFurnac
Fig. 21—2-Stage Furnacewith 1-Single Speed Heat Pump (Dual Fuel)A98095CORW2CRGYW/W1W2Y/Y2OBRHDEFDHUMHUMRVS COOLINGTWO-STAGEFURNACESINGLE-SPEED HEATPUM
Fig. 25—Variable-Speed Non-Condensing Furnacewith 1-Speed Heat Pump (Dual Fuel)A98099CCRYW/W1GW2Y/Y2OBRHRVS COOLINGVSP FURNACEBOARDSINGLE-SPEED HEATPU
Fig. 29—Variable-Speed 2-Stage CondensingFurnace — W/O DE Connection -with 1-Speed Heat Pump (Dual Fuel)A98103CCRW2W/W1GW2Y/Y2OBRHRVS COOLINGVSP SPEED
Fig. 33—Variable-Speed 2-Stage CondensingFurnace — With DE Connection —With 1-Speed Heat Pump (Dual Fuel)A99374CCRW2W/W1GW2Y/Y2OBRHRVS COOLINGVSP SPEE
Fig. 37—Typical Fan Coilwith 1-Speed Heat PumpA98107CRCRGW2YW2W3YEOBRHDEFRVS COOLINGTYPICAL FAN COILSINGLE-SPEEDHEAT PUMPEQUIPMENTCONTROLLERN/A24 V
Fig. 41—FK and FV Fan Coilwith 1-Speed Heat PumpA99369CW2OBRVS COOLINGN/AR1HFK AND FVSERIESFAN COILSINGLE-SPEEDHEAT PUMPREMOVEJ1 JUMPERREMOVEJ2 JUMPER
WIRING DIAGRAM NOTES1. Heat pump must have a high pressure switch for dual fuel applications.2. Outdoor Air Sensor must be attached for all dual fuel
1. Open doors or remove cover to access mounting holes(remove the 2 Zone system cover from the left side first).2. Mount back plate to wall using scre
3. Properly seal joint using duct tape, mastic, or other approvedmethod. Do not allow mastic to come in contact with actuator.4. Insulate damper using
4. Insulate damper using 1-1/2 in. to 2-in. insulation. (Checkyour local codes.) (See Fig. 8.)Step 5—Install Barometric Bypass DamperNOTE: The baromet
Carrier’s Comfort Heat system is now supported by Comfort ZoneII -B, with all the features of the Thermidistat™ Control. Whenused with compatible vari
than the coolest zone (in cooling) or warmer than the warmest zone(in heating). This prevents over conditioning of OUT zones whilestill using them to
heat. This acts to prevent the unnecessary use of auxiliary heat. Inaddition, when an outdoor sensor is attached, the system can be setto lock out aux
ON—Normal single system (address = 01).OFF—Address selection for second zoning system.Switch 6—Select installer test mode to assist in checking out th