Carrier 16JB Instrukcja Użytkownika Strona 25

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 28
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 24
The control center shall include a 16-line by
40-characterliquidcrystal display(LCD)screen,
four function keys, stop button, and alarm
light.The microprocessorshall beconfigurable
to display either English or SI metric units.
b. The default standard display screen shall si-
multaneously indicatethe followingminimum
information:
date and time of day
24-character primary system status
message
24-character secondary system status
message
chiller operating hours
entering chilled water temperature
leaving chilled water temperature
evaporator refrigerant temperature
entering absorber water temperature
leaving absorber water temperature
leaving condenser water temperature
strong solution temperature leaving
generator
weak solution temperature leaving
absorber
output signal to steam/hot water control
valve
The defaultscreen shallbe displayedif there
is no manual activity at the control console
for 15 minutes.
c. The 4 function keys shall be software driven
within the Status, Schedule, Set Point and
Service menu structures (as described below).
1) Status Function:
In addition to the default screen, status
screens shall be accessible to view the sta-
tus of every point monitored by the con-
trol center including:
refrigerant temperature
vapor condensate temperature
generator temperature
solution concentrations
capacity control valve position
control point settings
refrigerant level switches
solution pump starts
absorber loss
evaporator approach temperature
absorber and condenser approach
temperatures
discrete output status of various devices
2) Schedule Function:
The chiller controls shall be configurable
for manual or automatic startup and shut-
down. In automatic operation mode, the
controls shall be capable of automatically
starting and stopping the chiller accord-
ing to a stored user programmable
occupancy schedule.The controls shallin-
clude built-in provisions for accepting a
minimumoftwo365-day occupancysched-
ules. Each schedule shall allow a mini-
mum of 8 separate occupied and unoccu-
pied periods, any or all of which can be
scheduled by individual day for any or all
days of the week, with a separate sched-
ulefor holidays.Schedulesshallallow speci-
fication of daylight savings start/end and
up to 18 user-defined holidays up to one
year in advance (month, day, and dura-
tion in days). Display of the occupancy
schedules shall be viewable on the LCD
screen.Eachscheduleshall provideameans
of configuring an occupancy timed over-
ride to permit a ‘‘one time extension’’ of
an occupiedperiod on theconfigured day.
The controls shall also provide for chiller
start-up and shutdown via remote contact
closure from a customer supplied device,
or from a building management system
software command.
3) Set Point Function:
The controls shall provide the capability
to view and change the leaving chilled wa-
ter set point, entering chilled water set
point, and demand limit set point at any-
time during chiller operating or shutdown
periods. The controls shall allow for the
specification of capacity control via either
leaving chilled water or entering chilled
water.
4) Service Function:
The controlsshall providea password pro-
tected service function which allows au-
thorized individuals to:
view an alarm history file which shall
contain the last 25 alarm and/or alert
messages with time and date stamp.
Thesemessages shallbe displayedintext
form, not codes.
execute a chiller controls test function
for quick identification of malfunction-
ing components.
view and/or modify chiller
configuration.
view and/or modify chiller occupancy
periods.
view and/ormodify scheduleholiday pe-
riods.
view and/or modify schedule override
periods.
view and/or modify system time and
date.
25
Przeglądanie stron 24
1 2 ... 20 21 22 23 24 25 26 27 28

Komentarze do niniejszej Instrukcji

Brak uwag