QUALITY ASSURANCE
SYSTEM
38AJ 008-074 (R-22)
38AZ 008-074 (R-407C)
Air-Cooled Condensing Units
50 Hz
Installation, Operation and Maintenance Instructions
Przeglądanie stron 0
1 2 3 4 5 6 ... 15 16

Podsumowanie treści

Strona 1 - Air-Cooled Condensing Units

1QUALITY ASSURANCESYSTEM38AJ 008-074 (R-22)38AZ 008-074 (R-407C)Air-Cooled Condensing Units50 HzInstallation, Operation and Maintenance Instructions

Strona 2

10Fig. 4 - 38AJ/AZ 046-074, dual evaporatorLegend:A Suction riser without trapB Suction riser with trapC Suction riser line to condensing unit1 Evapor

Strona 3

11ACCESSORIESThe field-installed accessories are shipped with full installationinstructions and/or a wiring diagram.• Single- or two-stage low voltage

Strona 4 - 38AJ/AZ 030-036

12Pressure differential (difference between cylinderload point and unloader points)Turn the adjusting screw 햵 counter-clockwise to its back stoppositi

Strona 5

13SERVICING REFRIGERATION COMPONENTSAny technician attending the machine for any purpose must bea fully qualified refrigeration engineer.WARNING: Befo

Strona 6 - Electrical data

14CAUTION: R-22 oils are absolutely not compatible with R-407C.Recommended oil:R-22 semi-hermetic compressors:- Mineral oil, Carrier specification No.

Strona 7 - Standard unit 12 2 0

15For normal maintenance routines we recommend using 1 kg ofthe concentrated product, diluted to 10%, to treat a coil surfaceof 2 m2. This process ca

Strona 8

16ENVIRONMENTALMANAGEMENTTROUBLESHOOTING CHARTBelow we list a series of possible faults, along with the probable causes and suggested solutions. In th

Strona 9

2CONTENTSPageStart-up checklist ...

Strona 10 - Fig. 6 - Suction line piping

3START-UP CHECK LISTStart-up date:Equipment sold by: Contract No.:Installed by: Contract No.:Site address:Equipment type and serial numbers:Electrical

Strona 11

4Dimensions and clearances38AJ/AZ A B C D E F G008-012 1220 1160 977 1200 1000 1000 1000014-024 1720 1160 1112 1200 1000 1000 1000030-036 2060 1370 1

Strona 12

538AJ/AZ 04638AJ/AZ 062-074Do not obstructDo not obstructFloor mounting• For unit mounting holes, weight distribution and centre of gravity coordinate

Strona 13

6Physical data38AJ/AZ 008 010 012 014 018 024 030 036 046 062 074Nominal cooling capacity 38AJ* kW 23.3 29.4 36.5 51.0 61.0 76.0 93.0 119.0 139.0 170.

Strona 14 - Suction valve M16 135-140

7APPLICATION DATAOperating limitsVarifan III (option)The Carrier Varifan III allows adjustment of the fan speed or ofthe three-phase motors (400 V-3 p

Strona 15

8Refrigerant piping diagramSingle circuit only for 38AJ/AZ 008-036 unitsSoldered plug withpressure equalisationport. To be removedduring installation.

Strona 16 - MANAGEMENT

9• The second moisture indicator must be installed close tothe condenser to provide a means of checking therefrigerant charge.• Complete the liquid li