Carrier 40CS024 Instrukcja Obsługi Strona 7

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 6
Step 3Mounting the Air Conditioner On the Bracket
1. Remove the air conditioner front panel and air intake grille, as
shown in Fig. 5.
2. Fasten the left and right side strips to the air conditioner using
6 sheet metal screws, as shown in Fig. 19. Ensure that:
a. The wide side of the strip is located at the bottom of the air
conditioner.
b. The strip angle faces inward.
3. Mount the indoor unit on the bracket. Slide the protruding
parts of the side strips onto the ceiling bracket so that the 4
safety screw holes on the left and right strips align with those
on the ceiling bracket.
4. Make sure that the air conditioner is tilted slightly toward the
drainage outlet on the right side. Use water to test for proper
drainage. Fix the tilt by adjusting the height of the right strip
relative to the left one.
5. Fasten the air conditioner to the ceiling bracket using the 4
side screws. (See Fig. 20.)
Step 4Continuing the Installation
After attaching the air conditioner to the ceiling bracket, continue
the installation procedure in the previous section, titled
Drainage.
NOTE: If the drainage is routed in direction no. 1, as shown in
Fig. 16, cut out the oval opening in the air intake opening for the
drainage tube and route the tube through the air intake grille. (See
Fig. 21.)
NOTE: Set DIP switch no. 1 to the ON position. (See Fig. 11.)
The other factory switches are set at the factory and should not be
changed.
Step 5Installing the Outdoor Unit
1. The outdoor unit must be installed on a solid surface.
2. Make sure that the unit is level.
3. Fasten the outdoor unit legs to the base, as shown in Fig. 14.
Place the rubber absorption cushions (supplied with the
outdoor unit) under the units legs to prevent vibrations.
WIRING THE OUTDOOR UNIT
1. Remove the outdoor unit plastic side cover.
2. Loosen the screws on the terminal block.
3. Attach the electrical terminals supplied to the inter-unit
control and power cable wires.
4. Connect the wires to the terminal block, in accordance with
the coding which appears in Fig. 15.
5. Connect the outdoor sensor cable, making sure the connector
is properly inserted.
6. Secure the inter-unit electric and sensor cable to the outdoor
unit with the clamp shown in Fig. 14.
7. Reassemble the plastic side cover.
NOTE: A drainage tube can be connected to the outdoor unit to
remove condensation formed during heating mode operation.
Make sure that all screws and wires are properly fastened.
Loose wires or connections can cause damage and present a
fire hazard.
Step 6Connecting the Refrigerant Lines
1. To connect the refrigerant lines, use only L type sealed,
dehydrated copper refrigerant tubing. No other type of tubing
may be used. Use of other types of tubing will void the
manufacturers warranty.
2. Do not open service valves or remove protective caps from
tubing ends until all the connections are made.
3. Take care to avoid kinks or flattening of the tubing.
4. Bend tubing with special bending tools to avoid the formation
of sharp bends.
5. Keep the tubing free of dirt, sand, moisture, and other
contaminants to avoid damaging the refrigerant system.
6. Avoid sags in the suction line to prevent the formation of oil
traps.
7. Insulate the tubing with 3/8-in. walled thermal pipe insulation.
Inserting the tubing into the insulation before making the
connections will save time and improve installation. The
suction and liquid lines should never come in direct contact.
FLARING AND CONNECTING
1. Remove the protective cap from the flare fitting.
2. Remove the protective cap from the tubing and cut to the
required length. Make sure that the cut is perpendicular and
clean, without burrs.
3. Slip the flare nut on the tubing and flare the tube end, using
standard flaring tools.
4. Tighten the nut until resistance is met. Mark the nut and the
fitting. Using a suitable wrench tighten an additional 1/4 turn.
Use the following specified torque, according to connection
size:
Liquid line:
1/4-in. - (12.3 ft/lb)
3/8-in. - (29 ft/lb)
Suction line:
1/2-in. - (36 ft/lb)
5/8-in. - (47 ft/lb)
3/4-in. - (72 ft/lb)
5. The valves on the outdoor unit must remain closed until all
four connections have been made.
Step 7Air Vacuum and Refrigerant Charge
When all the fittings are connected, air must be expelled, as
follows:
1. Open the service port cap on the suction line valve (large
valve).
2. Connect the vacuum pump to the service port via the pressure
gauge and operate the pump for 15 minutes.
3. Make sure that full vacuum is present and disconnect the
vacuum pump.
Fig. 12Remoter Controller and Rack
A01157
WIRELESS REMOTE CONTROLLER
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
MODE FAN SWEEP
AA
START
STOP
1 2 3 SLEEP
DAILY
11:45
72
7
Przeglądanie stron 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 19 20

Komentarze do niniejszej Instrukcji

Brak uwag