18
Application data (cont)
ELASTOMERIC PAD
23XRV ISOLATION WITH ACCESSORY SOLEPLATE PACKAGE
TYPICAL ISOLATION
STANDARD ISOLATION
ACCESSORY SOLEPLATE DETAIL
VIEW X-X
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Accessory soleplate package includes 4 soleplates, 16 jacking screws and leveling
pads. Requires isolation package.
3. Jacking screws to be removed after grout has set.
4. Thickness of grout will vary, depending on the amount necessary to level chiller. Use
only pre-mixed non-shrinking grout, Ceilcote 748 or Chemrex Embeco 636 Plus
Grout, 0-1
1
/
2
(38.1) to 0-2
1
/
4
(57) thick.
5. Service clearance under the chiller is enhanced if leveling pads are not extended
along the entire length of the heat exchangers.
VIEW Y-Y
ISOLATION WITH ISO L ATI ON PAC K AGE O N LY
(STAN DA R D)
NOTE: Isolation package includes 4 elastomeric pads.