37A SeriesModulineAir DiffusersSelection and Installation manual

Strona 2

101.10 - Upstream air qualityAir filtersThe standard 50 mm air filters built into central station airhandlers may be of either the throwaway type or t

Strona 3 - Contents

112 - AIR THROWThe air stream moves horizontally beneath the false ceilinginducing more air from the room as it does so. This creates aslowly moving u

Strona 4

124 - SELECTION GUIDE4.1 - INTRODUCTIONEssential data :- Room dimensions- Specified or required noise level- Room design temperature- Heat gains and l

Strona 5

13Room B 109/57 = 1.91 hence use 2 37AG units.4. Calculate the air flow for each unitFor rooms A and C : 44/1 = 44 l/sFor room B : 109/2 = 55 l/s5. Ve

Strona 6

145 - PHYSICAL AND PERFORMANCE DATA5.1 - 37AG Moduline with 900 mm active length5.1.1 - General data- Nominal air flow 200 m3/h - 56 l/s- Maximum unit

Strona 7

155.1.4 - Sound power level 37AG with 900 mm active length5.1.3 - 37AG air throw - 900 mm active lengthLegend :1) Based upon tests according to ASHRAE

Strona 8 - = 1 x duct diameter

165.2 - 37AG Moduline with 1200 mm active length5.2.1 - General data- Nominal air flow 266 m3/h - 76 l/s- Maximum units per controller : 8- Air flow a

Strona 9 - 37AH units in ser

175.2.4 - Sound power level 37AG with 1200 mm active length5.2.3 - 37AG air throw - 1200 mm active lengthLegend :(1) Based upon tests according to ASH

Strona 10

185.3 - 37AS Moduline5.3.1 - General data- Nominal air flow 200 m3/h - 56 l/s- Not connectible in series- Air flow at shutoff: 41 m3/h - 11 l/s ± 3 l/

Strona 11

195.3.4 - Sound power level 37AG with 1200 mm active length5.3.3 - 37AS air throwLegend :(1) Based upon tests according to ASHRAE 36B-63 with standard

Strona 12 - 3,6 m 4,8 m

The photo shown on the front cover is solely for informa-tion, and not contractually binding. The manufacturerreserves the right to make changes witho

Strona 13

205.4 - 37AH Moduline5.4.1 - General data- Nominal air flow 350 m3/h - 97 l/s- Max number of units per controller: 4- Air flow at shutoff: 68 m3/h - 1

Strona 14 - VIEW ON V

215.4.4 - 37AH Sound power level 5.4.3 - 37AH air throwLegend :(1) Based upon tests according to ASHRAE 36B-63 with standard air and an ASHRAE sound r

Strona 15 - Legend :

225.5.2 - Physical data and dimensions5.5 - 37AHS Moduline5.5.1 - General data- Nominal air flow 325 m3/h - 90 l/s- Max number of units per controller

Strona 16 - EC : End Cap

23Note :Value determined by this curve is for one side of the diffuser only.5.5.4 - 37AHS sound power level 5.5.3 - 37AHS air throwLegend :(1) Based u

Strona 17

246 - CONTROLSModuline systems are essentially self regulating.The air pressure which is the controlling force is itself derivedfrom the primary air s

Strona 18

256.1.1 - Control accessories6.1.1.1 - Constant volume control kitThe control assembly comprises:- filter- constant volume controller- connection tube

Strona 19 - 5.3.3 - 37AS air throw

266.1.1.2 - Variable air volume controller with Moduline ther-mostatThe variable air volume controller assembly comprises :- filter- flow controller-

Strona 20

27AccessoriesPart N°37AE 900 592 C37AH 900 062 CDescriptionControl connectiontube 30,5 ml rollsTube bifurcator (Y)kit of 25 unitsApplicationUsed for c

Strona 21 - 5.4.3 - 37AH air throw

286.1.3 - Variable air volume control with a room thermostatFor greater accessibility, Carrier offers a high precision wallmounted thermostat with the

Strona 22 - * Without packaging

296.2 - Electronic controlElectronic control is recommended when a Moduline system isto operate either in conjunction with an on/off heating systemor

Strona 24 - Fig. 2 - Control schematic

30NOTE GÉNÉRALE:- With Moduline, the plug in controls are easily relocated or reconfigured. Partitions can be repositioned and spaces reallocat-ed to

Strona 25

317 - ACCESSORIES

Strona 26 - Variable volume

32EView on EFView on FInstalling alignment piecesNOTE:Refer to the return air diffuser dimensional drawings.

Strona 27

337.1 - Suspension accessories7.2 - Plenum accessories

Strona 28

347.2.1 - Control interconnections and combinations37AG master with 37AG slaves37AH master with 37AH slaveslegende :C Controller or controller with th

Strona 29

35NOTES:1. Diffuser length is given by module dimension (1200 mm) and diffuser type (discontinuous = module dimension - 25 mm) Inthis example the diff

Strona 30

368.2 - 37AH ModulineNOTES:1. Diffuser length is given by module dimension (1200 mm) and diffuser type (discontinuous = module dimension - 25 mm) Inth

Strona 31 - 7 - ACCESSORIES

378.3 - 37AHS ModulineNOTES:The diameters of the connection spigots depend upon the size of the plenum as shown by character positions 9 and 10.

Strona 32 - Installing alignment pieces

388.4 - 37AS ModulineNOTES:1. Diffuser length is given by module dimension (1200 mm) and diffuser type (discontinuous = module dimension - 25 mm) Inth

Strona 33 - 7.2 - Plenum accessories

399 - INSTALLATION INSTRUCTIONS9.1 - 37AG, AH, AS constant volume and variable volumeunits9.1.1 - IntroductionControllers can be installed in the unit

Strona 34 - 37AH master with 37AH slaves

41 - INTRODUCTION1.1 - Main featuresCarrier Moduline air conditioning terminals integrate air distri-bution and air volume flow control, constant volu

Strona 35

408 - Refer to Fig 3 or Fig 6 as appropriate. Remove the plugfrom the bellows connection, or from the Y bifurcator, accord-ing to type, and connect it

Strona 36

419.2 - 37AHS Constant volume and variable volume units9.2.1 - IntroductionControls can be installed in the units either before (to be pre-ferred) or

Strona 38

439.3 - Wall thermostats with 37AG, AH, AHS and ASunits9.3.1 - DescriptionThe thermostat is a proportional device which enables theleakage rate at shu

Strona 39 - Fig. 2 - 37AH Moduline

449.4.5 - ApplicationNOTE :Controller/amplifier to be ordered separatelyback view (wall side) front viewThermostat labelFixing slot 4.5 x 9.5 mmCover

Strona 40 - Fig 5 - 37AG unit detail

459.4 - Installing controller/amplifiers9.4.1 - IntroductionController/amplifier assemblies may be installed before (to bepreferred) or after installa

Strona 41

46Controller/amplifierController/amplifiermountingScrew GasketPlugFilterTubesPlugWall thermostatTo filterTo bellowsSWarm-up switchor min air flowcontr

Strona 42

479.5 - Installing the minimum air flow controller9.5.1 - IntroductionThe minimum air flow controller and, more often, a controlleron 37A units may be

Strona 43 - 37AG, AH, AHS, AS

489.6 - Installing the warm-up switch on 37AG, AH,AHS, AS units1. Remove the rubber plug from the plastic base of the thermo-stat to enable the 3/16 i

Strona 44 - 9.4.5 - Application

492 - Remove the brass cap from the controller bleed orifice.3 - Set the electronic interface on the central diffuser andconnect the 4 mm internal dia

Strona 45

5Nominal air flow: 267 m3/h - 74 l/sAir flow range: 90-627 m3/h - 25-173 l/sThe 37AG is suitable for all types of offices, commercialpremises, hospita

Strona 46

5010 - SITE WORKS : SUPPLY AIR FLOW MEASUREMENT10.1 - Velocity sensor locationHot wire anemometer (0-10 m/s)NOTE:Be careful, don’t take velocity readi

Strona 47

51Diffuser active lengthA 1 200 mmB 900 mmC 600 mm10.2 - Average air velocity per slot as a function of total air flow - 37AGDiffuser active lengthA 1

Strona 48

5210.3 - Average air velocity per slot as a function of total air flow - 37AHDiffuser active lengthA 1 200 mmB 900 mmC 600 mmDiffuser active lengthA 1

Strona 49

5311 - SPECIAL ORDER UNITS11.1 - Diffuser lengthDiffusers may be from 449.5 to 2000 mm long.11.2 - Surface finishDiffusers may be unpainted, anodised

Strona 50

5412 - SPECIFICATION GUIDESupply and install Moduline air terminal units with the con-trols and accessories required for the units to function as stan

Strona 51

No 13716-20, October 2000 - Supersedes No: 13716-20, April 1999Manufacturer reserves the right to change any product specification without notice.Manu

Strona 52

61.5 - Moduline in false ceilingsa. All 37 Series Moduline terminals can be integrated intofalse ceilings with removable tiles.b. Moduline terminals,

Strona 53

7Fig. 4 - Moduline units installed parallel to T-bars in a single storey buildingLocation Model Discharge Plenum Adapters Diffuserlength, mmG-1 37AG 1

Strona 54

81.6 - Special false ceilings and ModulineConsult Carrier SA, La Boisse before planning the use of Moduline with any special false ceiling.1.7 - Insta

Strona 55 - Printed in France

91.8 - Connecting Modulines in series. Sizing supplyair ductsWith the exception of the 37AS model, Moduline air terminalshave connection spigots at ea